Date |
Text |
2020-09-10 09:29:03 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF PRODUCT |
| APPROVALS/NOA'S FOR THE PROPOSED SLOPED ROOFING SYSTEM |
| USED. |
| 2. SUBMITTED MIAMI-DADE COUNTY NOA NO. 18-1127.18 |
| GENERAL LIMITATION #7 IS SPECIFICALLY REFERRED TO IN |
| THIS NOA. PERIMETER AND CORNER AREAS SHALL COMPLY WITH |
| THE ENHANCED UPLIFT PRESSURE REQUIREMENTS OF THESE |
| AREAS. FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| INSULATION AND BASE SHEET AS CALCULATED IN COMPLIANCE |
| WITH ROOFING APPLICATION STANDARD RAS 117. CALCULATIONS |
| PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, OR |
| REGISTERED ROOF CONSULTANT. PROVIDE. |
| |