Review Stop B
Sequence Number 1
Notes
Date Text
2020-09-10 09:29:03JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT PETER VALENTI (561) 805-6673
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED SLOPED ROOFING SYSTEM
 USED.
 2. SUBMITTED MIAMI-DADE COUNTY NOA NO. 18-1127.18
 GENERAL LIMITATION #7 IS SPECIFICALLY REFERRED TO IN
 THIS NOA. PERIMETER AND CORNER AREAS SHALL COMPLY WITH
 THE ENHANCED UPLIFT PRESSURE REQUIREMENTS OF THESE
 AREAS. FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION AND BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARD RAS 117. CALCULATIONS
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, OR
 REGISTERED ROOF CONSULTANT. PROVIDE.
  