Plan Review Notes For Permit 20071364 |
Permit Number |
20071364 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-09-04 11:06:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO INDICATIONS OF THE LOCATION OF THE | | TEMPORARY GENERATOR ON THE SITE PLAN. | | | | PLEASE PROVIDE A LOCATION WITH DIMENSION TO BUILDING | | AND INCLUDE SPARATION DISTANCE FROM ANY WINDOWS, DOORS | | OR A/C EQUIPMENT. | | | | | | 1A) IF IT IS PROPOSED IN THE PARKING LOT, PROVIDE | | PROTECTION FROM UNINTENDED VEHICLE IMPACT OR JUSTIFY | | WITH SPECIFIC NARRATIVE WHY PROTECTION WOULD NOT BE | | NEEDED. | | | | | | | | 2) PLEASE PROVIDE ANY MANUFACTURES SPECIFICATION SHEETS | | THAT INCLUDE FUEL TYPE, MOBILE/WHEELED OR STATIONARY. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|