Plan Review Notes For Permit 20071364 |
Permit Number |
20071364 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-08-21 08:44:40 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC R 301, PROVIDE A STRUCTURAL DETAIL FOR THE | | GENERATOR PAD AND ANCHORING. IF A FORMED AND POURED | | SLAB IS PROPOSED, THE DESIGN IS TO INCLUDE THE PRINTED | | NAME AND SIGNATURE OF THE INDIVIDUAL TAKING | | RESPONSIBILITY FOR THE DESIGN. | | | | IF A PREFAB SLAB IS PROPOSED, ENGINEERING IS REQUIRED. | | | | 2. FBC 107, PROVIDE A SURVEY SHOWING PROPOSED LOCATION | | OF THE GENERATOR. |
|