2020-08-10 15:46:04 | 08/10/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. SIGNED AND SEALED DRAWINGS NEED TO BE |
| DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW NOT IN |
| ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| 61G10-11.010 SEALS AND 61G15-23.005. |
| |
| 2. PLUMBING RISER DIAGRAM REQUIRED FOR AS BUILT PER THE |
| WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) |
| COMMERCIAL PLUMBING. |
| |
| 3. GAS RISER DIAGRAM REQUIRED FOR AS BUILT PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.5.1.5 (9) COMMERCIAL |
| GAS. |
| |
| 4. SUBMIT A NARRATIVE OF THE CHANGES MADE TO ALL PHASES |
| OF PLUMBING AND GAS FOR AS BUILT PER THE WPB AMENDMENTS |
| TO THE FBC WPB A 107.4. |
| |
| 5. PROVIDE A SHUT OFF VALVE SCHEDULE ON WHERE THE RISER |
| SHUT OFF VALVE TO EACH LOCATION WOULD BE AND TAG |
| DESCRIBING IT USE PER THE 2017 FBC SEC. P 606.4. |
| |
| 6. ON SHEET 027 PLEASE DELETE ALL LETTER CORRESPONDING |
| TO EACH SECTIONAL CUT OF PIPE AS THIS CLUTTER THE |
| DRAWING AND THE CLARITY IS OBSTRUCTED PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1.4 QUALITY OF |
| BUILDING PLANS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |