2020-08-14 11:33:24 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| A- PROPOSED REVISIONS TO APPROVED PLANS |
| |
| 1) REVISED SHEETS A111A&B, A121A&B, A181A&B HAVE THE |
| MECHANICAL DUCTS AND OTHER MECHANICAL INFORMATION ON |
| THEM. THESE ARE ARCHITECTURAL FLOOR PLANS. REVISED PLAN |
| SHEETS REPLACE THE ORIGINALS, THEREFORE THESE SHEETS |
| CAN NOT BE APPROVED BECAUSE REQUIRED FLOOR PLAN |
| INFORMATION IS OBSCURED BY THE MECHANICAL ITEM OVERLAY. |
| YOU WILL NEED TO REVISE THE APPROPRIATE MECAHNICAL |
| DRAWINGS OR SUBMIT THESE PLANS AS NEW SHEETS WITH |
| DIFFERENT SHEET NUMBERS AND MECHANICAL LABELS. CITY |
| AMENDMENTS FBC 107.2.1.3 |
| |
| 2) THE PLANS DO NOT HAVE THE ENGINEER'S OR ARCHITECT'S |
| DIGITAL SIGNATURE AS REQUIRED BY FS 471 AND 481. SEE |
| THE SIGNATURE REVIEW STOP. |
| |
| SHOP DRAWINGS: |
| |
| B - STRUCTURAL STEEL CALCULATIONS |
| |
| 1) THE ELECTRONICALLY SUBMITTED STEEL FRAMING |
| CALCULATIONS ARE REQUIRED TO HAVE (DEWEY A. LEBANC |
| P.E.) THE ENGINEER'S DIGITAL SIGNATURE. I WAS UNABLE TO |
| VERIFY THE SIGNATURE. FS 471 & FAC 61G-15 SEE THE |
| SIGNATURE REVIEW STOP. |
| |
| 2) THE STEEL FRAMING CALCULATIONS ARE REQUIRED TO BE |
| REVIEWED AND APPROVED BY THE DESIGNER OF RECORD |
| (ARCHITECT/ENGINEER OR BOTH) IN RESPONSIBLE CHARGE. |
| CITY AMENDMENTS FBC107.3.4.1 |
| |
| 3) PARTS OF THE STEEL FRAMING CALCULATIONS ARE NOT |
| LEGIBLE. CITY AMENDMENTS FBC 107.2.1 |
| |
| C - STEEL TRUSSES |
| |
| 1) THE ELECTRONICALLY SUBMITTED STEEL TRUSS DRAWINGS |
| ARE REQUIRED TO HAVE THE TRUSS ENGINEER'S DIGITAL |
| SIGNATURE. FS 471 & FAC 61G-15 SEE THE SIGNATURE REVIEW |
| STOP. |
| |
| 2) THE STEEL TRUSS DRAWINGS ARE REQUIRED TO BE REVIEWED |
| FOR CONFORMANCE WITH THE DESIGN OF THE BUILDING BY THE |
| DESIGNER OF RECORD (ARCHITECT/ENGINEER OR BOTH) IN |
| RESPONSIBLE CHARGE. CITY AMENDMENTS FBC107.3.4.1 |
| |
| 3) THE TRUSS PLACEMENT PLANS HAS AN ADDRESS OF 901 S |
| FLAGLER. THE ADDRESS OF THIS PROJECT IS 351 PEMBROKE |
| PLACE. CITY AMENDMENTS FBC 107.2.1.3 |
| |
| |
| |
| |
| |