2020-08-11 19:24:54 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT-20071234 |
| 8/11/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1- PLEASE INDICATE THE USE AND OCCUPANCY ON THE PLANS |
| |
| 2- A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| PLUMBING CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 105.1. |
| |
| 3- A SEPERATE PERMIT IS REQUIRED FOR THE GREASE |
| INTERCEPTOR. WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| |
| 4- INTERCEPTORS SHALL BE DESIGNED AND SIZED BY THE |
| GREASE INTERCEPTOR MANUFACTURE. FACTORY SIZING |
| CALCULATIONS REQUIRED FROM THE MANUFACTURE FBC 2017 P |
| 1003.2 |
| |
| 5- PROVIDE HIGH LOW DRINKING FOUNTAIN. PLEASE INDICATE |
| ON THE PLAN WHERE ONE WILL BE PROVIDED. FBC 2017 |
| A211.2, FBC 2017 P410.3 |
| |
| 6- PROVIDE SPECIFICATIONS FOR THE TANKLESS WATER HEATER |
| AND THE BACKFLOW DEVICE TO BE INSTALLED. |
| |
| 7- BAR AREA SHALL HAVE AN ACCESSIBLE TOP ELEVATION AS |
| PER FBC 2017 A 902.1 A902.2 A902.3 |
| |
| 8- CLEAR WASTE AND DRINKING FOUNTAIN SHALL NOT |
| DISCHARGE INTO GREASE INTERCEPTOR. REVISE PLUMBING |
| ISOMETRIC TO REFLECT DRINKING FOUNTAIN AND HAND SINK |
| DRAIN LINES CONNECTING TO SANITARY BUILDING MAIN DRAIN. |
| FBC P 1003.2 |
| |
| 9- PLUMBING SYSTEM SHALL HAVE NOT LESS THAN ONE VENT |
| PIPE THAT EXTENDS TO THE OUTDOORS FBC P 904.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |