Plan Review Notes
Plan Review Notes For Permit 20071234
Permit Number 20071234
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-07-28 10:31:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHET A 1.0 - THERE IS AN INDICATION OF BUSINESS
 OCCUPANCY. THIS APPEARS TO BE A CHANGE OF OCCUPANCY
 FROM THE PREVIOUS OCCUPANCY.
  
 PER NFPA 101, CH 6, THE OCCUPANCY IS ASSEMBLY AND SAHLL
 COMPLY WITH THE REQUIREMENTS OF NFPA 101, CH 12
  
 6.1.2.1* DEFINITION ? ASSEMBLY OCCUPANCY. AN OCCUPANCY
 (1) USED
 FOR A GATHERING OF 50 OR MORE PERSONS FOR DELIBERATION,
 WORSHIP,
 ENTERTAINMENT, EATING, DRINKING, AMUSEMENT, AWAITING
 TRANSPORTATION, OR
 SIMILAR USES; OR (2) USED AS A SPECIAL AMUSEMENT
 BUILDING, REGARDLESS OF
 OCCUPANT LOAD.
  
 PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET A 1.0 - THERE ARE NO DIMENSIONS PROVIDED TO
 CONFIRM OCCUPANCY LOAD AND EGRESS REQUIREMENTS OR THAT
 ALL THE INDICATED TABLES AND CHAIRS CAN FIT INTO THE
 SPACE AS PROPOSED.
  
 PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE.
  
  
 2 A ) SHEET A 1.0 - THERE IS AN INDICATION OF A BAR
 AREA WITH A WOOD BAR TOP, HOWEVER, THERE ARE NO
 INDICATIONS OF BAR STOOLS.
  
 PLEASE CONFIRM THAT BAR STOOLS WILL NOT BE PLACED AT
 THE BAR.
  
 IF PROPOSED, THEY SHALL BE INCLUDED IN THE FLOOR PLAN
 AND CONTAINED IN THE OCCUPANCY LOAD.
  
 PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE.
  
  
  
 3) SHEET A 1.0 - THERE IS AN INDICATION OF WHAT APPEARS
 TO BE A RAMP WITH RAILINGS; HOWEVER, THERE ARE NO
 DETAILS TO CONFIRM COMPLIANCE WITH THE LIFE SAFETY
 CODE.
  
 RAMPS AND RAILING SHALL COMPLY WITH NFPA 101 CH 7 MEANS
 OF EGRESS.
  
 7.2.2.4 GUARDS AND HANDRAILS.
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES,
 UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR
 7.2.2.4.1.6.
  
 7.5.5.3 NEW RAMPS SHALL BE IN ACCORDANCE WITH TABLE
 7.2.5.3(A),
 EXISTING RAMPS SHALL BE PERMITTED TO REMAIN IN USE OR
 BE
 REBUILT, PROVIDED THAT THEY MEET THE REQUIREMENTS SHOWN
 IN
 TABLE 7.2.5.3(B),
  
 PLEASE REVIEW, CORRECT, PROVIDE DETAILS AND ENSURE
 COMPLIANCE.
  
  
  
  
 4) SHEET A 1.0 - THERE IS AN INDICATION OF AN EXIT SIGN
 OVER AN EXTERIOR DOOR, HOWEVER, THERE IS NO DOOR
 SCHEDULE TO CONFIRM COMPLIANCE WITH THE EXIT DOOR
 HARDWARE, LOCKS OR LATCHES.
  
 PER NFPA 101 CH 7
  
 7.2 MEANS OF EGRESS COMPONENTS.
 7.2.1 DOOR OPENINGS.
 7.2.1.1 GENERAL.
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO
 THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE
 SPECIAL
 REQUIREMENTS OF 7.2.1.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE.
  
  
  
  
 4A) SHEET A 1.0 - THERE IS AN INDICATION OF A REAR
 42"X80" DOOR BUT THOUGH IT DOES NOT APPEAR TO BE AN
 EXIT DOOR, THERE IS NO INDICATION OF HARDWARE OR IF
 WILL BE A FUNCTIONING DOOR.
  
 PLEASE PROVIDE DETAILS.
  
  
  
  
 5) SHEET A 1.0 - THERE IS AN INDICATION OF A DOUBLE
 LINE AROUND THE PERIMETER OF THEOPEN PATIO.
  
 WHAT DOES THIS EXTERIOR FEATURE CONSIST OF? IS IT A
 RAILING, A HALF WALL, SINGLE POSTS WITH FULL OPENINGS?
  
 PLEASE REVIEW, CORRECT WITH DETAILS AND ENSURE
 COMPLIANCE WITH APPLICABLE CODES.
  
  
  
 6) SHEET A 1.0 - THERE ARE INDICATIONS OF TWO OVERHEAD
 DOORS THAT LEAD TO THE EXTERIOR PATIO, HOWEVER, THSES
 DOORS CAN NOT FUNCTION AS EXIT DOORS.
  
 TWO EXITS ARE REQUIRED IN AN ASSEMBLY OCCUPANCY AND
 THEY SHALL BE SEPARATED FROM EACH OTHER PER NFPA 101 CH
 12 & 7
  
 12.2.4* NUMBER OF MEANS OF EGRESS.
 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE
 WITH SECTION 7.4, OTHER THAN EXITS FOR FENCED OUTDOOR
 ASSEMBLY
 OCCUPANCIES IN ACCORDANCE WITH 12.2.4.4.
  
 12.2.5 ARRANGEMENT OF MEANS OF EGRESS.
 12.2.5.1 GENERAL.
 12.2.5.1.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH
 SECTION 7.5.
 12.2.5.1.2 A COMMON PATH OF TRAVEL SHALL BE PERMITTED
 FOR THE FIRST
 20 FT (6100 MM) FROM ANY POINT WHERE THE COMMON PATH
 SERVES
 ANY NUMBER OF OCCUPANTS, AND FOR THE FIRST 75 FT (23 M)
 FROM ANY
 POINT WHERE THE COMMON PATH SERVES NOT MORE THAN 50
 OCCUPANTS.
  
 7.4* NUMBER OF MEANS OF EGRESS.
 7.4.1 GENERAL.
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS
 THAN TWO,
 EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED
 IN CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE
 OR BALCONY WHERE THE COMMON PATH OF TRAVEL LIMITATIONS
 OF
 CHAPTERS 11 THROUGH 43 ARE MET.
  
 7.5 ARRANGEMENT OF MEANS OF EGRESS.
 7.5.1 GENERAL.
 7.5.1.1 EXITS SHALL BE LOCATED, AND EXIT ACCESS SHALL
 BE ARRANGED, SO
 THAT EXITS ARE READILY ACCESSIBLE AT ALL TIMES.
  
 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH
 7.5.1.3.1
 THROUGH 7.5.1.3.7.
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS
 REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH
 EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE
 POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER
 EMERGENCY
 CONDITION.
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE
 REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE
 ANOTHER NOT
 LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL
 DIMENSION OF THE BUILDING OR AREA TO BE SERVED,
 MEASURED IN A
 STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS,
 EXIT ACCESSES, OR
 EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3
 THROUGH
 7.5.1.3.5.
  
 PLEASE REVIEW AND CORRECT
  
  
 6A) SHEET A 1.0 - THERE ARE INDICATIONS OF TWO OVERHEAD
 DOORS THAT LEAD TO THE EXTERIOR PATIO, HOWEVER, THERE
 IS NO INDICATIONS OF THE DEPTH, IF ANY, OF THE STEP
 DOWN.
  
 PLEASE PROVIDE DETAILS.
  
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  