2020-07-28 10:31:11 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHET A 1.0 - THERE IS AN INDICATION OF BUSINESS |
| OCCUPANCY. THIS APPEARS TO BE A CHANGE OF OCCUPANCY |
| FROM THE PREVIOUS OCCUPANCY. |
| |
| PER NFPA 101, CH 6, THE OCCUPANCY IS ASSEMBLY AND SAHLL |
| COMPLY WITH THE REQUIREMENTS OF NFPA 101, CH 12 |
| |
| 6.1.2.1* DEFINITION ? ASSEMBLY OCCUPANCY. AN OCCUPANCY |
| (1) USED |
| FOR A GATHERING OF 50 OR MORE PERSONS FOR DELIBERATION, |
| WORSHIP, |
| ENTERTAINMENT, EATING, DRINKING, AMUSEMENT, AWAITING |
| TRANSPORTATION, OR |
| SIMILAR USES; OR (2) USED AS A SPECIAL AMUSEMENT |
| BUILDING, REGARDLESS OF |
| OCCUPANT LOAD. |
| |
| PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE. |
| |
| |
| |
| 2) SHEET A 1.0 - THERE ARE NO DIMENSIONS PROVIDED TO |
| CONFIRM OCCUPANCY LOAD AND EGRESS REQUIREMENTS OR THAT |
| ALL THE INDICATED TABLES AND CHAIRS CAN FIT INTO THE |
| SPACE AS PROPOSED. |
| |
| PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE. |
| |
| |
| 2 A ) SHEET A 1.0 - THERE IS AN INDICATION OF A BAR |
| AREA WITH A WOOD BAR TOP, HOWEVER, THERE ARE NO |
| INDICATIONS OF BAR STOOLS. |
| |
| PLEASE CONFIRM THAT BAR STOOLS WILL NOT BE PLACED AT |
| THE BAR. |
| |
| IF PROPOSED, THEY SHALL BE INCLUDED IN THE FLOOR PLAN |
| AND CONTAINED IN THE OCCUPANCY LOAD. |
| |
| PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE. |
| |
| |
| |
| 3) SHEET A 1.0 - THERE IS AN INDICATION OF WHAT APPEARS |
| TO BE A RAMP WITH RAILINGS; HOWEVER, THERE ARE NO |
| DETAILS TO CONFIRM COMPLIANCE WITH THE LIFE SAFETY |
| CODE. |
| |
| RAMPS AND RAILING SHALL COMPLY WITH NFPA 101 CH 7 MEANS |
| OF EGRESS. |
| |
| 7.2.2.4 GUARDS AND HANDRAILS. |
| 7.2.2.4.1 HANDRAILS. |
| 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON |
| BOTH SIDES, |
| UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR |
| 7.2.2.4.1.6. |
| |
| 7.5.5.3 NEW RAMPS SHALL BE IN ACCORDANCE WITH TABLE |
| 7.2.5.3(A), |
| EXISTING RAMPS SHALL BE PERMITTED TO REMAIN IN USE OR |
| BE |
| REBUILT, PROVIDED THAT THEY MEET THE REQUIREMENTS SHOWN |
| IN |
| TABLE 7.2.5.3(B), |
| |
| PLEASE REVIEW, CORRECT, PROVIDE DETAILS AND ENSURE |
| COMPLIANCE. |
| |
| |
| |
| |
| 4) SHEET A 1.0 - THERE IS AN INDICATION OF AN EXIT SIGN |
| OVER AN EXTERIOR DOOR, HOWEVER, THERE IS NO DOOR |
| SCHEDULE TO CONFIRM COMPLIANCE WITH THE EXIT DOOR |
| HARDWARE, LOCKS OR LATCHES. |
| |
| PER NFPA 101 CH 7 |
| |
| 7.2 MEANS OF EGRESS COMPONENTS. |
| 7.2.1 DOOR OPENINGS. |
| 7.2.1.1 GENERAL. |
| 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL |
| CONFORM TO |
| THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE |
| SPECIAL |
| REQUIREMENTS OF 7.2.1. |
| |
| 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| READILY FROM |
| THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| |
| PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE. |
| |
| |
| |
| |
| 4A) SHEET A 1.0 - THERE IS AN INDICATION OF A REAR |
| 42"X80" DOOR BUT THOUGH IT DOES NOT APPEAR TO BE AN |
| EXIT DOOR, THERE IS NO INDICATION OF HARDWARE OR IF |
| WILL BE A FUNCTIONING DOOR. |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| |
| |
| 5) SHEET A 1.0 - THERE IS AN INDICATION OF A DOUBLE |
| LINE AROUND THE PERIMETER OF THEOPEN PATIO. |
| |
| WHAT DOES THIS EXTERIOR FEATURE CONSIST OF? IS IT A |
| RAILING, A HALF WALL, SINGLE POSTS WITH FULL OPENINGS? |
| |
| PLEASE REVIEW, CORRECT WITH DETAILS AND ENSURE |
| COMPLIANCE WITH APPLICABLE CODES. |
| |
| |
| |
| 6) SHEET A 1.0 - THERE ARE INDICATIONS OF TWO OVERHEAD |
| DOORS THAT LEAD TO THE EXTERIOR PATIO, HOWEVER, THSES |
| DOORS CAN NOT FUNCTION AS EXIT DOORS. |
| |
| TWO EXITS ARE REQUIRED IN AN ASSEMBLY OCCUPANCY AND |
| THEY SHALL BE SEPARATED FROM EACH OTHER PER NFPA 101 CH |
| 12 & 7 |
| |
| 12.2.4* NUMBER OF MEANS OF EGRESS. |
| 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| ACCORDANCE |
| WITH SECTION 7.4, OTHER THAN EXITS FOR FENCED OUTDOOR |
| ASSEMBLY |
| OCCUPANCIES IN ACCORDANCE WITH 12.2.4.4. |
| |
| 12.2.5 ARRANGEMENT OF MEANS OF EGRESS. |
| 12.2.5.1 GENERAL. |
| 12.2.5.1.1 MEANS OF EGRESS SHALL BE ARRANGED IN |
| ACCORDANCE WITH |
| SECTION 7.5. |
| 12.2.5.1.2 A COMMON PATH OF TRAVEL SHALL BE PERMITTED |
| FOR THE FIRST |
| 20 FT (6100 MM) FROM ANY POINT WHERE THE COMMON PATH |
| SERVES |
| ANY NUMBER OF OCCUPANTS, AND FOR THE FIRST 75 FT (23 M) |
| FROM ANY |
| POINT WHERE THE COMMON PATH SERVES NOT MORE THAN 50 |
| OCCUPANTS. |
| |
| 7.4* NUMBER OF MEANS OF EGRESS. |
| 7.4.1 GENERAL. |
| 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY, |
| MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS |
| THAN TWO, |
| EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS: |
| (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE |
| PERMITTED |
| IN CHAPTERS 11 THROUGH 43. |
| (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A |
| MEZZANINE |
| OR BALCONY WHERE THE COMMON PATH OF TRAVEL LIMITATIONS |
| OF |
| CHAPTERS 11 THROUGH 43 ARE MET. |
| |
| 7.5 ARRANGEMENT OF MEANS OF EGRESS. |
| 7.5.1 GENERAL. |
| 7.5.1.1 EXITS SHALL BE LOCATED, AND EXIT ACCESS SHALL |
| BE ARRANGED, SO |
| THAT EXITS ARE READILY ACCESSIBLE AT ALL TIMES. |
| |
| 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH |
| 7.5.1.3.1 |
| THROUGH 7.5.1.3.7. |
| 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| EXIT DISCHARGE IS |
| REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH |
| EXITS, EXIT ACCESSES, |
| OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH |
| OTHER AND BE |
| ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| HAS THE |
| POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER |
| EMERGENCY |
| CONDITION. |
| 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| DISCHARGES ARE |
| REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE |
| ANOTHER NOT |
| LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL |
| DIAGONAL |
| DIMENSION OF THE BUILDING OR AREA TO BE SERVED, |
| MEASURED IN A |
| STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS, |
| EXIT ACCESSES, OR |
| EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3 |
| THROUGH |
| 7.5.1.3.5. |
| |
| PLEASE REVIEW AND CORRECT |
| |
| |
| 6A) SHEET A 1.0 - THERE ARE INDICATIONS OF TWO OVERHEAD |
| DOORS THAT LEAD TO THE EXTERIOR PATIO, HOWEVER, THERE |
| IS NO INDICATIONS OF THE DEPTH, IF ANY, OF THE STEP |
| DOWN. |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| |
| |
| |
| 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |