2020-09-10 15:04:02WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20071220
 ADD: 2020 OR 2062 PALM BEACH LAKES BLVD.
 CONT: MIKE MOORE CONSTRUCTION
 TEL: 561-301-9468
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. SEPT. 10TH/ 2020
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST. 1ST ROUND COMMENTS. SHEET 3.1 IS THE
 LIFE SAFETY SHEET. THIS SHEET INDICATES WITH A NOTE
 THIS IS TO BE A 150 SEAT RESTAURANT. THE FLOOR PLAN
 DOES NOT SHOW COMPLIANCE FOR ANY ACCESSIBLE SEATING.
  
 2A) 2ND REQUEST. RESPONSE INDICATES SEE NEW UPDATED 3,1
 SHEET. SHEET 3.1 STILL SHOWS DATE 7/27/2020, NOT
 UPDATED. NO VERSION 2.
 1ST ROUND OF COMMENTS. ACCESSIBILITY CODE. 226.1 WHERE
 DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF
 FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES
 AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. 150 X 0.05= 7.5 OR 8 SEATS. (YOU ROUND UP TO
 THE NEXT WHOLE PERSON).
  
 2B) 2ND REQUEST. RESPONSE INDICATES SEE NEW UPDATED 3,1
 SHEET. SHEET 3.1 STILL SHOWS DATE 7/27/2020, NOT
 UPDATED.
 2017 ACCESSIBILITY CODE 226.2 DISPERSION. DINING
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES INCLUDING BARS, SEASONAL SEATING, ETC?.
  
 2C) 2ND REQUEST. RESPONSE INDICATES SEE NEW UPDATED 3,1
 SHEET. SHEET 3.1 STILL SHOWS DATE 7/27/2020, NOT
 UPDATED.
 2017 ACCESSIBILITY CODE 206.2.5 206.2.5 RESTAURANTS AND
 CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS,
 INCLUDING RAISED OR SUNKEN DINING AREAS, AND OUTDOOR
 DINING AREAS.
  
 2D) 2ND REQUEST. RESPONSE INDICATES SEE NEW UPDATED 3,1
 SHEET. SHEET 3.1 STILL SHOWS DATE 7/27/2020, NOT
 UPDATED.
 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. DINING
 SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES,
 LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK SURFACES
 INCLUDE WRITING SURFACES,
  
 2D)(1) 2ND REQUEST. RESPONSE INDICATES SEE NEW UPDATED
 3,1 SHEET. SHEET 3.1 STILL SHOWS DATE 7/27/2020, NOT
 UPDATED.
 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 SHALL BE PROVIDED. KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
  
 2D)(2) 2ND REQUEST. RESPONSE INDICATES SEE NEW UPDATED
 3,1 SHEET. SHEET 3.1 STILL SHOWS DATE 7/27/2020, NOT
 UPDATED.
 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PLEASE SEE
 SHEET 3.3 BAR COUNTER TOPS DETAILS 6 ,9? 10, 11 & 12.
  
 2E) 2ND REQUEST. RESPONSE INDICATES SEE NEW UPDATED 3,1
 SHEET. SHEET 3.1 STILL SHOWS DATE 7/27/2020, NOT
 UPDATED.
 THE FRONT ENTRY IS ASSUMED TO BE A LEVEL FLOOR SURFACE
 FROM THE EXTERIOR TO THE INTERIOR WITH NO MORE THAN A ?
 INCH THRESHOLD, BUT THE PLANS ARE SILENT AS TO THE
 REQUIRED REAR EXIT FOR THE PUBLIC.
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS TO
 THE PUBLIC WAY.
  
 3A-C) COMPLIED.
  
 4A) PROVISO/ DEFERRED SUBMITTAL. EXTERIOR DOOR (NOA
 19-1016.03).
 4B) PROVISO. W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE
 CODE RULE 61G20 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 5) 2ND REQUEST. RESPONSE LETTER INDICATES THE WIND
 DESIGN CRITERIA IS GIVEN ON THE NEW 3,1 SHEET. SHEET
 3.1 STILL SHOWS DATE 7/27/2020, NOT UPDATED. NO VERSION
 2.
 WITH THE REPLACEMENT OF AN EXTERIOR DOOR THERE SHOULD
 BE WIND DESIGN CRITERIA PROVIDED. 2017 FBC-B 1603.1.4
 WIND DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO
 WIND LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND
 LOADS GOVERN THE DESIGN OF THE LATERAL FORCE-RESISTING
 SYSTEM OF THE STRUCTURE:
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 5.2. RISK CATEGORY.
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
 5.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO
 CONTACT ME, MY CELL NUMBER IS 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER