Plan Review Notes
Plan Review Notes For Permit 20071220
Permit Number 20071220
Review Stop P
Sequence Number 1
Notes
Date Text
2020-08-12 10:55:511ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20071220
 8/11/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1 & P2 SANITARY ISOMETRIC: A) THE WATER
 CLOSET (P-1) AT WOMEN 111 IS NOT BEING VENTED BECAUSE
 IT IS NOT CONNECTING DIRECTLY INTO THE HORIZONTAL WET
 VENTED BRANCH LINE SERVING P-3 AND THE FD. AN
 INDIVIDUAL VENT IS REQUIRED IF IT IS TO BE CONNECTED
 DIRECTLY INTO THE MAIN DRAIN. B) THE HORIZONTAL WET
 VENTED SYSTEM SERVING WOMEN 112 APPEARS TO BE
 NON-COMPLIANT BECAUSE THE DRAIN LINES FOR P-3 AND THE
 LOWER P-1 ARE EACH CONNECTING VERTICALLY INTO THE
 BRANCH DRAIN LINE AND HORIZONTAL CONNECTIONS ARE
 REQUIRED- SECTIONS 912.1, 912.2 & 912.2.1 FBC P. C)
 IDENTIFY THE FIXTURE NEXT TO THE ICE MAKER.
  
 2) P1: THE MAKE, MODEL AND CAPACITY OF THE EXISTING
 GREASE INTERCEPTOR MUST BE NOTED ON THE PLANS- SECTIONS
 1003.3.4 AND 1003.3.6. THE PLAN SHOWS NEW FLOOR SINKS
 BELOW FOOD AND BEVERAGE PREP COUNTERS,
 THREE-COMPARTMENT SINKS, AND ALSO IN THE CENTER OF THE
 COMMERCIAL KITCHEN BELOW THE STEAM TABLE ALL OF WHICH
 ARE DRAINING INTO THE SANITARY INSTEAD OF THE GREASY
 WASTE LINE. PLEASE REFER TO SECTION 1003.3.1 REVISE THE
 PLANS AND SIZING CALCULATIONS ACCORDINGLY.
  
 3) P-2: SUBMIT PRODUCT SPECIFICATION SHEETS FOR THE
 WATER HEATERS, AND EQUIPMENT SCHEDULES THAT INCLUDE THE
 EFFICIENCY RATINGS OF THE UNITS- SECTION C404.22 FBC
 EC. REFER TO TABLE 604.3 AND PROVIDE CALCULATIONS TO
 VERIFY THE EXISTING WATER HEATER SERVING THE PLUMBING
 FIXTURES IN THE KITCHEN AND BAR AREA HAS THE REQUIRED
 CAPACITY.
  
 4) P-2: PROVIDE A PLUMBING DEVICE SCHEDULE THAT
 INCLUDES THE BACKFLOW PREVENTERS AND WATER HAMMER
 ARRESTORS- SEE SECTION 604.9 & TABLE 608.1.
  
 5) SHEET 3.3: THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSET IN THE MEN'S TOILET 106 COMPARTMENT SHALL BE 60
 INCHES WIDE MINIMUM MEASURED PERPENDICULAR TO THE SIDE
 WALL, AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED
 WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL
 SECTION 604.8.1.1 FBC ACC.
  
 6) 3.3: SHOW THE REQUIRED TURNING SPACES IN THE TOILET
 ROOMS AND COMPARTMENT- SECTION 304.3 AND FIGURE
 604.8.1.6
  
 7) 3.3: KNEE AND TOE CLEARANCES FOR THE LAVATORIES ARE
 NOT SHOWN- SECTION 306.
  
 8) 3.3: THE REAR GRAB BEHIND THE WATER CLOSET SHALL BE
 POSITIONED IN COMPLIANCE WITH FIGURE 604.5.2.
  
 9) 3.3: THE HEIGHT OF THE GRAB BARS SHALL BE 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE PLAN
 SHOWS THE MEASUREMENT TO THE CENTERLINE OF THE BARS-
 SECTION 609.4.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  