2020-08-05 17:43:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) HI LIGHT OR CIRCLE ALL OF THE APPROPIATE ITEMS IN
 THE PRODUCT APPROVAL INCLUDING THE DESIGN PRESSURE AND
 TYPE OF INSULATION. FBC 107.2
  
 2) THE ROOFING SYSTEM THAT WAS SUBMITTED TYPE A(4) ON
 PAGES15-16 OF THE PRODUCT APPROVAL REQUIRES AT LEAST
 ONE LAYER OF THE LISTED INSULATIONS. THE MAXIMUM DESIGN
 PRESSURE FOR THIS SYSTEM IS -60 PSF, WHICH IS TOO LOW
 FOR THE PERIMETER AND CORNER ROOF AREAS. THE LIMITATION
 #7 REQUIRES THAT SIGNED AND SEALED CALCULATIONS ARE
 SUBMITTED FOR ENHANCED FASTENING IN THESE AREAS TO
 INCREASE THE DESIGN PRESSURES. SUBMIT THE REQUIRED
 DOCUMENTS. FBC 107.2
  
 3) SUBMIT A ROOF DIAGRAM OF THE BUILDING. SPECIFY THE
 ROOF HEIGHT AND SHOW DIMENSIONS OF THE ROOF. INDICATE
 ANY ROOF DRAINS, PARAPET WALLS, SCUPPERS, ETC. FBC
 107.2.1