2020-08-06 16:31:46 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- PLUMBING PLAN REVIEW |
| W. P. B. PERMIT PRIME: 20071161 |
| W. P. B. PLUMBING PERMIT: 20071163 |
| ADD: 550 OKEECHOBEE BLVD. |
| PLUMB.CONT: SBL CONSTRUCTION GROUP |
| TEL: 561-676-6060 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. AUGUST 06/2020 |
| ACTION: DENIED |
| |
| 1) THERE WERE NO PLANS SUBMITTED FOR PLUMBING. THE |
| PLUMBING CONTRACTOR MUST DRAW THEIR OWN PLANS FOR THE |
| SHOWER PAN. |
| CERTIFICATION BY CONTRACTOR. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATIVE CODE. 107.3.4.3 |
| CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE EXCEPTION |
| TO ENGINEERED PLANS UNDER 471.003(H) ELECTRICAL/ |
| PLUMBING/ MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES |
| THE CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN |
| THAT TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS |
| THE SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER) |
| THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO |
| IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE |
| PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR |
| THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH |
| TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER |
| THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR |
| NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE |
| DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED |
| AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO |
| SUBMIT ALL THESE TRADES UNDER ONE SHEET. |
| |
| 2) PLEASE PROVIDE DETAILS FOR THE SHOWER PAN COMPLYING |
| WITH SECTION 417.5.2 OF THE 2017 FBC-P. |
| |
| 3) THE SCOPE OF WORK INDICATES THE SHOWER VALVE IS TO |
| BE REPLACED BUT DOES NOT PROVIDE THE SPEC SHEET ON THE |
| SHOWER VALVE AND COMPLIANCE WITH SECTION 424.3 |
| INDIVIDUAL SHOWER VALVES 2017 FBC-P. SHOWER VALVES |
| SHALL BE REQUIRED WITH A MEANS TO LIMIT THE MAXIMUM |
| SETTING OF THE VALVE TO 120 DEGREES FAHRENHEIT. |
| |
| 4) PLEASE SHOW ON THE FLOOR PLAN WHICH WALL WILL HAVE |
| THE SHOWER VALVE AND SHOWER HEAD. AGAIN THE CONCERN IS |
| IF THEY ARE IN THE FIRE RATED WALL PROTECTION AROUND |
| THE OPENING IN THE 1 HOUR FIRE PARTITION. SHOW |
| COMPLIANCE WITH THE 2017 FBC-B 708.7 PENETRATIONS. |
| PENETRATIONS OF FIRE RATED WALLS SHALL COMPLY WITH |
| SECTION 714. |
| SEE 714.3.2 MEMBRANE PENETRATIONS. |
| |
| 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |