Date |
Text |
2020-08-11 10:04:24 | |
| WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20071096 |
| ADD: 1551 N FLAGLER DR. SUITE # 805 |
| CONT: LA ROCCCA CONSTRUCTION LLC |
| TEL: 954-980-0755 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. AUGUST 11TH/ 2020 |
| ACTION: DENIED |
| 1) PLANS THAT ARE NOT DESIGNED BY ARCHITECTS OR |
| ENGINEERS BUT BY CONTRACTORS MUST COMPLY WITH THE |
| FOLLOWING REQUIREMENTS. 107.3.4.3 CERTIFICATION BY |
| CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED |
| PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/ |
| MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE |
| CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT |
| TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE |
| SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER) |
| THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO |
| IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE |
| PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR |
| THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH |
| TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER |
| THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR |
| NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE |
| DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED |
| AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO |
| SUBMIT ALL THESE TRADES UNDER ONE SHEET. |
| 2) THE PERSON UPLOADING PLANS AND DOCUMENTS HAS LOADED |
| THE DOCUMENTS WRONG. FOR EXAMPLE FOR THEE FLOOR |
| UNDERLAYMENTS DO NOT LOAD THEM ONE PAGE AT A TIME. ONE |
| TEST ONE FOLDER. THIS GOES FOR ALL OTHER DOCUMENTS, YOU |
| MAY NEED TO CONTACT THE LIBRIAN TO SEE IF ALL OF THE |
| DOCUMENTS IN THE FILE FOLDER CAN BE ELIMINATED TO START |
| OVER. |
| 107.2.1.3. QUALITY OF PLANS THE BUILDING OFFICIAL MAY |
| ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS FOR |
| THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE |
| CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD |
| MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH |
| THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| |
| 3) OF THE 86 PAGES WHICH WERE LOADED SIDEWAYS PLEASE |
| LOAD THEM SO THEY DO NOT NEED TO EACH ONE BE TURNED TO |
| REVIEW THE DOCUMENTS. |
| 107.2.1.3. QUALITY OF PLANS. THE BUILDING OFFICIAL MAY |
| ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS FOR |
| THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE |
| CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD |
| MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH |
| THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| 4) THE FLOOR PLAN DOES NOT INDICATE AS TO WHAT TYPE OF |
| FLOOR UNDERLAYMENT IS BEING INSTALLED NOR THE FINISH |
| MATERIAL. PLEASE ADD THIS TO THE FLOOR PLAN. 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| 5) IN FINDING THE 2ND PAGE OF ONE OF THE FLOOR |
| UNDERLAYMENT REPORTS IT IS FOR THE WRONG FLOOR SYSTEM. |
| THE REPORT INDICATES IT IS FOR A 6 INCH CONCRETE SLAB, |
| BAR JOIST A DROPPED CEILING CAVITY OF 14 INCHES WITH 4 |
| INCHES OF INSULATION IN THE DROPPED CEILING CAVITY AND |
| ? IN DRY WALL. THIS BUILDING HAS A 6 INCH CONCRETE SLAB |
| ONLY, NO BAR JOIST AND NO DROPPED CEILING THROUGH THE |
| WHOLE SUITE. |
| FLOOR INSULATION (FBC-B 2017) |
| FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING |
| COMPLIANCE WITH: |
| |
| TYPE I AND II BUILDINGS |
| 5A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 5B) FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 5C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| LVT & LPT LUXURY VINYL TILE. FLOOR FINISH |
| CLASSIFICATION AS REQUIRED IN SECTION 804.2 |
| CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF |
| THE 2017 FBC-B. |
| |
| 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |