2020-07-29 09:55:55 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE TPO ROOF SYSTEM SELECTED ON PAGE 64 OF PRODUCT | | APPROVAL FL14083.1 SPECIFIES CELCORE LIGHT WEIGHT | | CONCRETE (LWC) WITH PRODUCT APPROVAL NUMBER FL2037 (SEE | | NOTE 15). THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR | | THE LWC IS NOA NO. 18-0717.05. IT IS PREFERABLE THAT | | THE PRODUCT APPROVALS FOR A ROOFING SYSTEM ARE EITHER | | ALL FL # OR MIAMI-DADE NOA AS SOME HAVE DIFFERENT | | REQUIREMENTS. THE DESIGNER OF RECORD CAN PROVIDE A | | LETTER STATING THAT THE LWC IN MIAMI DADE NOA NO. | | 18-0717.05 IS EQUAL TO FL 2037 AND IS ACCEPTABLE FOR | | THIS PROJECT. FBC 107 | | | | 2) THE PAGE FROM FL 14083.1 THAT HAS NOTE A REFERENCED | | IN THE TABLE ON PAGE 64 FOR THIS SYSTEM APPEARS TO BE | | MISSING FROM THE SUBMITTAL. FBC 107 | | | | 3) HI LIGHT OR CIRCLE THE ITEMS THAT APPLY TO THIS | | INSTALLATION ON PRODUCT APPROVAL NOA NO. 18-0717.05 FOR | | THE LWC. FBC 107.2.1 | | | | 4) THE ROOF PLANS FOR THIS BUILDING SHOWS WALKING PADS. | | SHOW HOW THE TPO MEMBRANE WILL BE DESIGNED IN THESE | | AREAS TO PREVENT DAMAGE FROM THE WALKING PADS. FBC 107 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. |
|