Plan Review Notes
Plan Review Notes For Permit 20071040
Permit Number 20071040
Review Stop B
Sequence Number 1
Notes
Date Text
2020-07-31 13:39:23SHUTTERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES OR ASSEMBLIES? NEEDS TO BE FILLED OUT CORRECTLY
 AND PRECISELY - IN THE SUBSTRATE COLUMN SHOW
 (TOP/BOTTOM) (CONCRETE/BLOCK OR BLOCK/BLOCK ETC.)
 SHUTTER CONNECTION TYPE A IS FOR CONCRETE AS SHOWN ON
 THE CHART PG. 12 OF 20 - THE ANCHOR EDGE DISTANCE NEEDS
 TO BE MULTIPLIED BY (.90) ACCORDING TO THE EDGE
 DISTANCE CHART ON PG.13 OF 20 BECAUSE YOU ARE USING
 "TAPCON WITH ADVANCED THEADFORM TECHNOLOGY" WHICH HAS A
 MINIMUM EDGE DISTANCE OF 3 1/2" - PLEASE REVISE THE
 FORM TO SHOW CORRECT "EDGE DISTANCE" "ANCHOR SPACING
 PER EDGE DISTANCE FACTOR AND ANCHOR TYPE"
 2) PLEASE SHOW THE DISTANCE FROM THE CORNER OF THE
 BUILDING TO THE EDGE OF THE WINDOW OPENING - NEEDED TO
 DETERMINE IF IN WIND ZONE 4 OR 5
  