Plan Review Notes For Permit 20071040 |
Permit Number |
20071040 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-31 13:39:23 | SHUTTERS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE | | DEVICES OR ASSEMBLIES? NEEDS TO BE FILLED OUT CORRECTLY | | AND PRECISELY - IN THE SUBSTRATE COLUMN SHOW | | (TOP/BOTTOM) (CONCRETE/BLOCK OR BLOCK/BLOCK ETC.) | | SHUTTER CONNECTION TYPE A IS FOR CONCRETE AS SHOWN ON | | THE CHART PG. 12 OF 20 - THE ANCHOR EDGE DISTANCE NEEDS | | TO BE MULTIPLIED BY (.90) ACCORDING TO THE EDGE | | DISTANCE CHART ON PG.13 OF 20 BECAUSE YOU ARE USING | | "TAPCON WITH ADVANCED THEADFORM TECHNOLOGY" WHICH HAS A | | MINIMUM EDGE DISTANCE OF 3 1/2" - PLEASE REVISE THE | | FORM TO SHOW CORRECT "EDGE DISTANCE" "ANCHOR SPACING | | PER EDGE DISTANCE FACTOR AND ANCHOR TYPE" | | 2) PLEASE SHOW THE DISTANCE FROM THE CORNER OF THE | | BUILDING TO THE EDGE OF THE WINDOW OPENING - NEEDED TO | | DETERMINE IF IN WIND ZONE 4 OR 5 | | |
|