2023-03-02 14:07:20 | 2ND PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| COMMENT NOT ADDRESSED - THIS COMMENT IS NOT FOR PUBLIC |
| HAND WASHING REQUIREMENTS. THIS COMMENT IS FOR HOT |
| WATER. A THERMOSTATIC MIXING VALVE NEEDS TO BE AT THE |
| WATER HEATER FOR HOT WATER SUPPLY, NOT TEMPERED WATER |
| DELIVERY. THE WATER HEATER DETAIL NEEDS TO SHOW A |
| MIXING VALVE. |
| 1. 2020 FPC 607.1.1 - HOT WATER DELIVERY - PER THIS |
| SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT |
| SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER |
| DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE. |
| THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE |
| INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1. |
| THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC |
| HANDWASHING PROTECTION FOR TEMPERED WATER. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |