Plan Review Notes For Permit 20071007 |
Permit Number |
20071007 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-03-09 16:50:28 | 2ND REVIEW FMC | | PERMIT: 20071007 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE OUTDOOR AIR CALCULATIONS SHALL BE CALCULATED | | BASED ON THE OCCUPANCY CLASSIFICATION AND THE OCCUPANT | | DENSITY FROM FMC TABLE 403.3.1.1 AND NOT THE ARCHITECTS | | EGRESS COUNTS. FMC 403.3.1.1 | | | | 2) SHOW THE REQUIRED DUCT SMOKE DETECTORS FOR THE RTUS | | THAT SHARE SUPPLY AIR. FMC 606.2.2 | | | | 3) PROVIDE THE ACCESS ON THE DRAWING FOR THE SERVICING | | OF THE ROOFTOP UNITS. FMC 306.5 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|