2023-03-09 16:50:282ND REVIEW FMC
 PERMIT: 20071007
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OUTDOOR AIR CALCULATIONS SHALL BE CALCULATED
 BASED ON THE OCCUPANCY CLASSIFICATION AND THE OCCUPANT
 DENSITY FROM FMC TABLE 403.3.1.1 AND NOT THE ARCHITECTS
 EGRESS COUNTS. FMC 403.3.1.1
  
 2) SHOW THE REQUIRED DUCT SMOKE DETECTORS FOR THE RTUS
 THAT SHARE SUPPLY AIR. FMC 606.2.2
  
 3) PROVIDE THE ACCESS ON THE DRAWING FOR THE SERVICING
 OF THE ROOFTOP UNITS. FMC 306.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  