Plan Review Notes
Plan Review Notes For Permit 20071007
Permit Number 20071007
Review Stop B
Sequence Number 2
Notes
Date Text
2023-03-08 08:12:09NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE REQUIRED ROOF DRAINAGE OVERFLOW
 SCUPPERS - FBC 1503.4.2.1 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 2) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK
 (FL10264) - THE ROOFING SYSTEM CIRCLED HAS A PRESSURE
 OF (-37.5 *) WHICH DOES NOT MEET THE REQUIRED WIND
 PRESSURES SHOWN ON DRAWING S1.
  
 3) ALL PRODUCT APPROVALS IN PROJECTDOX NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD
 OR LISTED ON THE DRAWINGS BY THE PRODUCT APPROVAL
 NUMBER - FBC WPB 107.3.4
  
 4) PLEASE PROVIDE THE EXTERIOR DOOR PRODUCT APPROVAL
 LISTED ON THE DRAWINGS.