2023-01-12 09:40:26NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE REQUIRED ROOF DRAINAGE OVERFLOW
 SCUPPERS - FBC 1503.4.2.1
  
 2) PLEASE SHOW THE WALLS SURROUNDING THE MOP SINK TO
 COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 3) DOORS LABELED (11) AND (12) ARE IN A SERIES AND
 REQUIRE MORE SPACE BETWEEN THEM - FBC ACCESSIBILITY
 404.2.6 DOORS IN SERIES AND GATES IN SERIES.
 THE DISTANCE BETWEEN TWO HINGED OR PIVOTED DOORS IN
 SERIES AND GATES IN SERIES SHALL BE 48 INCHES (1220 MM)
 MINIMUM PLUS THE WIDTH OF DOORS OR GATES SWINGING INTO
 THE SPACE.
  
 4) PLEASE SHOW THE WALL INSULATION TYPE AND "R" VALUE -
 FBC ENERGY
  
 5) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK
 (FL10284) AND (FL10264) - PLEASE CIRCLE THE ROOFING
 SYSTEM TO BE USED IN THE ROOFING PRODUCT APPROVAL -
 ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL MAY REQUIRE ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL - SEE
 GENERAL NOTES IN THE PRODUCT APPROVAL.
  
 6) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE DESIGNER OF RECORD OR LISTED ON THE
 DRAWINGS BY THE PRODUCT APPROVAL NUMBER - FBC WPB
 107.3.4
  
 7) THE HIGHER ROOF DOES NOT SHOW THE DECK TYPE - FBC
 107
  
 8) PLEASE SHOW THE WALL SHEATHING ATTACHMENT TYPE, SIZE
 AND ON CENTER SPACING TO METAL FRAMING - FBC 107
  
 9) BUILDING CONSTRUCTION TYPE IS SHOWN AS IIB - PLYWOOD
 WALL SHEATHING SHOULD BE SHOWN AS FIRE RETARDANT - FBC
 603.1
  
 10) PLEASE SHOW THE CEILING HEIGHT FOR THE ROOMS
 TOWARDS THE REAR OF THE BUILDING - FBC 1208.2
  
 11) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" WHEN REFERRING TO THE MIRROR
 HEIGHT FROM THE FLOOR - FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 12) EXTERIOR ALUMINUM SIDING IS SUBJECT TO WIND LOADS -
 PLEASE PROVIDE ATTACHMENT DETAILS OR PRODUCT APPROVALS
 - FBC 107
  
 13) SEPARATE PERMITS ARE REQUIRED FOR - EXISTING
 BUILDING DEMO., PARKING LOT, SITE WALLS/SCREEN WALLS.