2020-07-31 12:51:05 | SHUTTERS |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) NEED TO DETERMINE IF SHUTTERS ARE IN WIND ZONE 4 OR |
| 5. PLEASE PROVIDE A FLOOR PLAN FOR THE ENTIRE BUILDING |
| SHOWING THE LOCATION OF THE UNIT IN THE BUILDING. |
| CORNER UNITS NEED TO SHOW THE DISTANCE FROM THE EDGE OF |
| THE SHUTTER TO THE CORNER OF THE BUILDING. ALSO SHOW |
| THE WIDTH AND LENGTH OF THE ENTIRE BUILDING AND THE |
| MEAN ROOF HEIGHT. IF THE SHUTTERS ARE IN WIND ZONE 5 |
| THE ANCHOR SPACING SHOWN ON THE "SCHEDULE FOR |
| INSTALLATION OF OPENING PROTECTIVE DEVICES OR |
| ASSEMBLIES" IS INCORRECT. |
| 2) THE SIGNED AND SEALED WIND DESIGN CHART = SIGNED AND |
| SEALED DRAWINGS IN PROJECTDOX NEED TO BE |
| DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. |
| DRAWINGS DO NOT SHOW IN "ADOBE READER" AS |
| DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR |
| ENGINEER OR ARCHITECT DOES NOT HAVE AN ELECTRONIC OR |
| DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP |
| BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS |
| ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE |
| REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN |
| REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING |
| [email protected] AND ASKING FOR THE FORM |