Plan Review Notes For Permit 20071003
Permit Number 20071003
Review Stop B
Sequence Number 1
Notes
Date Text
2020-07-31 12:51:05SHUTTERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) NEED TO DETERMINE IF SHUTTERS ARE IN WIND ZONE 4 OR
 5. PLEASE PROVIDE A FLOOR PLAN FOR THE ENTIRE BUILDING
 SHOWING THE LOCATION OF THE UNIT IN THE BUILDING.
 CORNER UNITS NEED TO SHOW THE DISTANCE FROM THE EDGE OF
 THE SHUTTER TO THE CORNER OF THE BUILDING. ALSO SHOW
 THE WIDTH AND LENGTH OF THE ENTIRE BUILDING AND THE
 MEAN ROOF HEIGHT. IF THE SHUTTERS ARE IN WIND ZONE 5
 THE ANCHOR SPACING SHOWN ON THE "SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES OR
 ASSEMBLIES" IS INCORRECT.
 2) THE SIGNED AND SEALED WIND DESIGN CHART = SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER OR ARCHITECT DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM