Plan Review Notes
Plan Review Notes For Permit 20070979
Permit Number 20070979
Review Stop B
Sequence Number 2
Notes
Date Text
2020-08-19 14:01:00SHUTTERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1. FBC R 301, COMPLETE THE FORM PROVIDED AT THE FRONT
 COUNTER "SCHEDULE FOR INSTALLATION OF OPENING
 PROTECTIVE DEVICES OR ASSEMBLIES" FORM OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET)
  
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE FACTORS APPLY DEPENDING ON SUBSTRATE, EDGE
 DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON,
 BE SPECIFIC AS TO WHICH TAPCON (TAPCON W/ADVANCED
 THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
  
 FORMS CAN BE PROVIDED BY EMAILING [email protected] AND ASKING
 FOR "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES OR ASSEMBLIES" FORM.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved