Plan Review Notes For Permit 20070941 |
Permit Number |
20070941 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-30 14:34:31 | SHUTTERS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1. FBC R 301, COMPLETE THE FORM PROVIDED AT THE FRONT | | COUNTER "SCHEDULE FOR INSTALLATION OF OPENING | | PROTECTIVE DEVICES OR ASSEMBLIES" FORM OR PROVIDE ALL | | INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL | | SPREADSHEET) | | | | 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE | | NOTE FACTORS APPLY DEPENDING ON SUBSTRATE, EDGE | | DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON, | | BE SPECIFIC AS TO WHICH TAPCON (TAPCON W/ADVANCED | | THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR). | | | | 3. PLEASE SHOW THE DISTANCE FROM THE EDGE OF THE WINDOW | | TO THE EDGE OF THE BUILDING - FOR THE WINDOWS NEXT TO | | THE CORNERS - NEEDED TO DETERMINE WIND ZONE 4 OR 5. | | | | FORMS CAN BE PROVIDED BY EMAILING [email protected] AND ASKING | | FOR "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE | | DEVICES OR ASSEMBLIES? FORM. | | |
|