2020-07-29 18:41:50 | CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| 7/29/2020 1ST GAS REVIEW **DENIED** WITH COMMENTS NOTE |
| - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME |
| AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. THERE ARE |
| SEVERAL EXPIRED PERMITS IN THE SYSTEM FOR THIS ADDRESS. |
| PLEASE EMAIL: [email protected] TO GET THESE |
| RESOLVED. |
| |
| 1- I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND |
| THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF |
| ANY GAS AT THIS ADDRESS.SINCE THERE IS NO RECORD OF A |
| PERMIT FOR THE GAS, THE EXISTING GAS LINES SHALL |
| CONSIDERED AS NEW. WPB AMENDMENTS TO THE FBC SEC. |
| 105.1. |
| |
| 2- LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FUEL GAS |
| SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) |
| THROUGH 402.4 (37) OR 2017 FBC FUEL GAS RES. SEC. |
| G2413. |
| |
| 3- INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC FUEL GAS SEC. 402.2 OR 2017 |
| FBC FUEL GAS RES. SEC. G2413.2. |
| |
| 4- SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC. |
| 409.4, FBC FUEL GAS RES. SEC. G2420.4. |
| |
| 5- SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR |
| 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| |
| 5- THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES |
| 2017 FBC FUEL GAS SECS. 401.4, 401.8, 402.1, 402.2, |
| 402.3 OR 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8, |
| G2413.1, G2413.2, G2413.3. |
| |
| 6- SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC |
| FUEL GAS RES. SEC. G2421.1. |
| |
| 7- THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE |
| ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE |
| THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, |
| THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| OPERATING SYSTEM. 2017 FBC FUEL GAS SEC. 401.4, 401.8, |
| 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS SECS.G2412.4, |
| G2412.8, G2413.1, G2413.2, G2413.3. |
| |
| 8- WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| ATELYO BELISLE |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 1:00 PM TO 4:00 PM |