Plan Review Notes For Permit 20070907 |
Permit Number |
20070907 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2020-09-17 14:11:23 | PLAN REVIEW / BUILDING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | NEC 2014 | | | | 4TH REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | NOTE: 1 - A PRE-FAB GENERATOR PAD IS BEING PROPOSED: | | | | NOTE: 2 - ENGINEERING FOR THE PRE-FAB GENERATOR PAD HAS | | BEEN PREPARED BY A PROFESSIONAL ENGINEER. A VALID | | SIGNATURE AND SEAL IS REQUIRED. SEE COMMENTS UNDER | | SIGNATURE REVIEW. | | | | 1. THE WEIGHT OF THE PROPOSED 22KW GENERATOR IS 445LBS. | | THE MINIMUM WEIGHT REQUIRED ON THE PAD ENGINEERING IS | | 526LBS. | | | | 2. THE TOTAL WEIGHT ON THE GENERATOR PAD ENGINEERING | | (UNIT + PAD) STATES 460LBS. THE WEIGHT OF THE PROPOSED | | GENERATOR (445LBS), PLUS THE WEIGHT OF THE PAD (240LBS) | | WOULD BE 685LBS. | | PLEASE CLARIFY. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | |
|