 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 4TH REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTE: 1 - A PRE-FAB GENERATOR PAD IS BEING PROPOSED:
  
 NOTE: 2 - ENGINEERING FOR THE PRE-FAB GENERATOR PAD HAS
 BEEN PREPARED BY A PROFESSIONAL ENGINEER. A VALID
 SIGNATURE AND SEAL IS REQUIRED. SEE COMMENTS UNDER
 SIGNATURE REVIEW.
  
 1. THE WEIGHT OF THE PROPOSED 22KW GENERATOR IS 445LBS.
 THE MINIMUM WEIGHT REQUIRED ON THE PAD ENGINEERING IS
 526LBS.
  
 2. THE TOTAL WEIGHT ON THE GENERATOR PAD ENGINEERING
 (UNIT + PAD) STATES 460LBS. THE WEIGHT OF THE PROPOSED
 GENERATOR (445LBS), PLUS THE WEIGHT OF THE PAD (240LBS)
 WOULD BE 685LBS.
 PLEASE CLARIFY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  