2020-08-28 13:18:321ST REVIEW FBC-2017 RES.
 PERMIT- 20070889
 8/28/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) LP GAS TANK AND LP REGULATOR SPECS HAVE BEEN
 SUBMITTED WHICH ARE NOT RELEVANT TO THE NATURAL GAS
 GENERATOR INSTALLATION. I AM NOT ABLE TO SEPARATE OUT
 THE RELEVANT SUBMITTALS IN THE PACKAGE YOU SUBMITTED SO
 PLEASE SEPARATELY RESUBMIT THE DORMONT FLEX CONNECTOR
 AND THE PE PIPING SPECS. ONCE THOSE ARE RECEIVED THE
 INITIAL PACKAGE SENT WILL BE VOIDED- SECTION 107.2.1
 WPB.
  
 2) GAS SURVEY: PLEASE SUBMIT THE GENERAC MANUFACTURER'S
 GUIDELINES FOR INSTALLATION CLEARANCES TO VERIFY THE
 CLEARANCES SPECIFIED ON THE DRAWING. THE GUIDELINES CAN
 SUPERSEDE THE MINIMUM 10 FT. CLEARANCE TO OPERABLE
 OPENINGS INTO THE BUILDING PER SECTION R303.5.1 FBC
 RES.
  
 3) GAS RISER:
  
 A) PROVIDE THE DELIVERY PRESSURE AT THE METER- SECTIONS
 G2413.2, G2413.4.1 & G2413.5 FBC RES.
  
 B) PROVIDE THE TOTAL DEVELOPED LENGTH FROM THE METER TO
 THE MOST REMOTE APPLIANCE- PLEASE INCLUDE THE BRANCH
 LINE TO THE POOL HEATER WHICH IS NOT SHOWN ON THE
 RISER- SECTIONS G2413.4.1 & G2413.2.
  
 C) PROVIDE THE PIPE SIZING TABLES LISTED UNDER SECTION
 G2413.4. PLEASE NOTE THAT THE TABLE 402.4(3) FROM THE
 FBC FG SUBMITTED WITH THE REGULATOR SPECS CANNOT BE
 USED BECAUSE PIPE SIZING SHALL BE DONE ACCORDING TO THE
 TABLES IN THE FBC RES. THERE IS NO RELEVANT TABLE IN
 THE FBC RES THAT ALLOWS THE 3.0 IN. WC PRESSURE DROP.
 PLEASE SEE TABLE G2413.4(1) WHICH INDICATES A TYPICAL
 0.5 IN. WC PRESSURE DROP FOR RESIDENTIAL APPLIANCES,
 AND REFER TO SECTION G2413.5 FOR FURTHER CLARIFICATION.
 PLEASE NOTE THAT THE TABLES IN THE FBC FG CAN BE USED
 IF THE RELEVANT TABLE IS CONTAINED IN THE FBC RES SUCH
 AS TABLE G2413.4(1) & {402.4(2)}.
  
 4) PLEASE RESUBMIT THE REGULATOR SPECS MARKED UP TO
 SHOW MODEL, PRESSURE DROP, AND SPRING SELECTIONS. IN
 LIEU OF MARKING UP THE SPECS, PLEASE PROVIDE THE
 INFORMATION ON THE RESUBMITTED RISER DRAWING- SECTIONS
 G2421.1 & G2421.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  