Plan Review Notes
Plan Review Notes For Permit 20070888
Permit Number 20070888
Review Stop G
Sequence Number 1
Notes
Date Text
2020-07-21 13:44:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
  
 20070888 815 NATHAN HALE RD
  
 1ST REVIEW
  
 GAS COMMENTS:
  
 1. THE GAS TANK-LESS WATER HEATER IS NOTED AS FUTURE.
 IF THE CURRENT PERMIT IS OPEN A REVISION WILL BE
 REQUIRED TO SHOW THE INSTALLATION OF THE APPLIANCE. IF
 PERMIT IS CLOSED WITHOUT INSTALLATION OF SAID
 APPLIANCE, A NEW GAS PERMIT APPLICATION, PLAN AND
 MANUFACTURER'S SPECIFICATION SHEETS / INSTALLATION
 MANUAL SHALL BE SUBMITTED FOR THE INSTALLATION.
 ADDITIONALLY, IN EITHER CASE A PLUMBING PERMIT
 APPLICATION, PLAN AND UPDATED MANUFACTURER'S
 SPECIFICATION SHEETS / INSTALLATION MANUAL SHALL BE
 SUBMITTED AT THE TIME OF REVISION OR NEW PERMIT.
 2. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT INCLUDING THE
 FUTURE TANK-LESS WATER HEATER TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, FBC FG 402.2, AND 301.3 OR
 FBC RES G2404.3. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION PER FBC FG.305.1 AND FBC RES G2408.1.
 3. PER WPB FBC 107.2.1, INDICATE ON THE RISER DIAGRAM
 THE TYPE OF GAS (LP OR NATURAL).
 4. SHOW ON THE HOUSE PLAN THE LOCATION OF THE TANKLESS
 WATER HEATER AND THE LOCATION AND DISTANCE OF ANY
 OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE
 HOUSE PLAN DOES NOT SPECIFICALLY STATE THE BBQ AND THE
 FUTURE GAS TANKLESS WATER HEATER LOCATION; THE RISER
 DIAGRAM AND THE SURVEY DO NOT CORRESPOND WITH EACH
 OTHER. RECONCILE ALL THREE DOCUMENTS TO SHOW
 CONSISTENCY OF PIPE ROUTING SAND APPLIANCE LOCATION.
 5. SUBMITTAL FOR REGULATORS DOES NOT INDICATE THAT THEY
 ARE APPROVED FOR OUTDOOR INSTALLATION. PER WPB FBC
 107.2.1, PROVIDE DOCUMENTATION THAT REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING ARE APPROVED
 FOR OUTDOOR INSTALLATION AS REQUIRED BY FBC FG 410.1 OR
 FBC RES G2421.1.
 6. PER WPB 107.2.1, SHOW THE DISTANCE FROM THE MP
 REGULATOR TO THE APPLIANCE(S). PROVIDE MATERIAL TYPE(S)
 AND SIZING TABLE(S) FOR THE SAME. COMPLY WITH FBC FG.
 402.4 OR FBC RES G2413.4 FOR THE PROPER PIPE SIZE AND
 BTU LOAD.
 7. SEE WPB FBC 107.3.4.3 CERTIFICATION BY CONTRACTOR.
 PLEASE NOTE THE EXCEPTION TO ENGINEERED PLANS UNDER
 471.003(H) ELECTRICAL/ PLUMBING/ MECHANICAL,
 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR
 THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL
 ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER
 THAT TRADE. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN. FOR EACH TRADE THE
 CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER THE TRADE
 LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR NAME AND
 LICENSE NUMBER. AS THE PLANS ARE NOT DIGITALLY SIGNED,
 THE APPLICANT SHALL PROVIDE SIGNED PAPER DOCUMENT PRIOR
 TO PERMIT ISSUANCE. CALL 561-805-6724 FOR ADDITIONAL
 INFORMATION.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE GAS/PLUMBING
 PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR
 THE PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION
 NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR
 LICENSED IN THAT TRADE.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH