Plan Review Notes
Plan Review Notes For Permit 20070880
Permit Number 20070880
Review Stop B
Sequence Number 2
Notes
Date Text
2020-10-16 14:31:43PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 109.3, THE VALUATION OF THE PROJECT APPEARS TO
 BE LOW. PROVIDE A BREAK DOWN OF THE VALUATION INCLUDING
 ALL MATERIAL, LABOR & SERVICES INVOLVED.
  
 2) FBC B 107, PROVIDE A REPORT FROM AN ACCEPTABLE
 LICENSED COMPANY SHOWING THE LOCATION OF POST TENSION
 CABLES (X-RAYED OR OTHER ACCEPTABLE METHOD). THIS IS TO
 AVOID DAMAGE TO CABLES DURING PENETRATION OF SLAB.
  
 3) FBC B 714.4.1.2, FBC B TABLE 601, PROVIDE
 INFORMATION OF MATERIAL TO BE USED TO SEAL THE FLOOR
 PENETRATIONS (2HR RATING REQUIRED).
  
 4) FBC B 2509.2, PROVIDE INFORMATION AS TO THE TYPE OF
 WATER RESISTANT WALL BOARD THAT WILL BE USED IN THE WET
 AREAS OF THE EXTENDED SHOWER SPACE.
  
 5) FBC B 1207.2, 1207.2 & 603.1, THE FOLLOWING TESTS
 ARE REQUIRED AT THE NEW FLOORING AREAS (EXISTING BATH
 TUB AREA).
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) :
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 NOTE: PLEASE FEEL FREE TO CONTACT ME IF YOU ARE UNSURE
 ABOUT AN ACCEPTABLE FLOOR UNDERLAYMENT.
  