Plan Review Notes
Plan Review Notes For Permit 20070880
Permit Number 20070880
Review Stop P
Sequence Number 1
Notes
Date Text
2020-08-19 14:01:401) THIS BUILDING WAS ORIGINALLY BUILT AND DESIGNED
 UNDER THE FAIR HOUSING ACT GUIDELINES AND THE LEVEL OF
 ACCESSIBILITY CANNOT BE DECREASED.THE PLANNED
 ALTERATIONS TO THE MASTER BATH DO NOT COMPLY WITH THE
 REQUIREMENTS OF THE FAIR HOUSING ACT GUIDELINES.
 2) A 30 INCH WIDE BY 48 INCH DEEP CLEAR FLOOR SPACE IS
 REQUIRED ADJACENT TO THE SHOWER AND FLUSH WITH THE
 CONTROL WALL OF THE SHOWER PER FIGURE 7 (D) OF THE FAIR
 HOUSING ACT GUIDELINES REQUIREMENT # 7.
 3) REINFORCEMENT FOR THE LATER INSTALLATION OF GRAB
 BARS IN THE SHOWER IS REQUIRED PER THE FAIR HOUSING ACT
 REQUIREMENT # 6. SUBMIT AN ELEVATION DETAIL SHOWING THE
 LOCATION, LENGTH, WIDTH AND TYPE OF REINFORCEMENT TO BE
 INSTALLED. REFER TO FAIR HOUSING ACT GUIDELINES FIGURE
 #5.
 4) THE HEIGHT OF THE VANITIES SHALL NOT EXCEED 34
 INCHES PER THE FAIR HOUSING ACT GUIDELINES REQUIREMENT
 #7 (B) (V). SHOW THIS ON THE FLOOR PLAN.
 5) VANITIES AND LAVATORIES SHALL BE INSTALLED WITH THE
 CENTERLINE OF THE FIXTURE A MINIMUM OF 1 FOOT 3 INCHES
 HORIZONTALLY FROM AN ADJOINING WALL OR FIXTURE PER THE
 FAIR HOUSING ACT GUIDELINES REQUIREMENT #7 (B) (V).
 6) IF KNEESPACE IS NOT PROVIDED BELOW THE VANITY A 30
 INCHES WIDE MINIMUM BY 48 INCHES DEEP MINIMUM SHALL BE
 PROVIDED PARALLEL TO THE VANITY AND THE CLEAR FLOOR
 SPACE SHALL BE CENTERED ON THE COMPLIANT LAVATORY. FHA
 GUIDELINES REQUIREMENT #7 (B) (V) AND FIGURE 37 (C).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  