2020-08-19 14:01:40 | 1) THIS BUILDING WAS ORIGINALLY BUILT AND DESIGNED |
| UNDER THE FAIR HOUSING ACT GUIDELINES AND THE LEVEL OF |
| ACCESSIBILITY CANNOT BE DECREASED.THE PLANNED |
| ALTERATIONS TO THE MASTER BATH DO NOT COMPLY WITH THE |
| REQUIREMENTS OF THE FAIR HOUSING ACT GUIDELINES. |
| 2) A 30 INCH WIDE BY 48 INCH DEEP CLEAR FLOOR SPACE IS |
| REQUIRED ADJACENT TO THE SHOWER AND FLUSH WITH THE |
| CONTROL WALL OF THE SHOWER PER FIGURE 7 (D) OF THE FAIR |
| HOUSING ACT GUIDELINES REQUIREMENT # 7. |
| 3) REINFORCEMENT FOR THE LATER INSTALLATION OF GRAB |
| BARS IN THE SHOWER IS REQUIRED PER THE FAIR HOUSING ACT |
| REQUIREMENT # 6. SUBMIT AN ELEVATION DETAIL SHOWING THE |
| LOCATION, LENGTH, WIDTH AND TYPE OF REINFORCEMENT TO BE |
| INSTALLED. REFER TO FAIR HOUSING ACT GUIDELINES FIGURE |
| #5. |
| 4) THE HEIGHT OF THE VANITIES SHALL NOT EXCEED 34 |
| INCHES PER THE FAIR HOUSING ACT GUIDELINES REQUIREMENT |
| #7 (B) (V). SHOW THIS ON THE FLOOR PLAN. |
| 5) VANITIES AND LAVATORIES SHALL BE INSTALLED WITH THE |
| CENTERLINE OF THE FIXTURE A MINIMUM OF 1 FOOT 3 INCHES |
| HORIZONTALLY FROM AN ADJOINING WALL OR FIXTURE PER THE |
| FAIR HOUSING ACT GUIDELINES REQUIREMENT #7 (B) (V). |
| 6) IF KNEESPACE IS NOT PROVIDED BELOW THE VANITY A 30 |
| INCHES WIDE MINIMUM BY 48 INCHES DEEP MINIMUM SHALL BE |
| PROVIDED PARALLEL TO THE VANITY AND THE CLEAR FLOOR |
| SPACE SHALL BE CENTERED ON THE COMPLIANT LAVATORY. FHA |
| GUIDELINES REQUIREMENT #7 (B) (V) AND FIGURE 37 (C). |
| |