Plan Review Notes For Permit 20070871 |
Permit Number |
20070871 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-08-10 10:14:05 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR PAD ENGINEERING THAT WAS SUBMITTED | | REQUIRES THE 22KW GENERATOR TO HAVE A MINIMUM WEIGHT OF | | 466 LB. AND THE SPECIFICATIONS THAT WERE SUBMITTED FOR | | THE GENERAC 22KW GENERATOR LISTS THE WEIGHT FOR THIS | | GENERATOR AS 445 LBS. THEREFORE, IT DOES NOT MEET THE | | MINIMUM WEIGHT REQUIREMENT OF THE ENGINEERING. FBC 107 |
|