2020-08-10 10:14:05PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD ENGINEERING THAT WAS SUBMITTED
 REQUIRES THE 22KW GENERATOR TO HAVE A MINIMUM WEIGHT OF
 466 LB. AND THE SPECIFICATIONS THAT WERE SUBMITTED FOR
 THE GENERAC 22KW GENERATOR LISTS THE WEIGHT FOR THIS
 GENERATOR AS 445 LBS. THEREFORE, IT DOES NOT MEET THE
 MINIMUM WEIGHT REQUIREMENT OF THE ENGINEERING. FBC 107