Plan Review Notes
Plan Review Notes For Permit 20070839
Permit Number 20070839
Review Stop B
Sequence Number 2
Notes
Date Text
2020-09-08 07:47:50JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT PETER VALENTI (561) 805-6673
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1.FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN
 HEADING ?ANCHOR SPACING?; PROVIDE INFORMATION FROM PAGE
 FROM PAGE 9 OF FL13757-R6. EXAMPLE: LOAD (P.S.F.)
 +53.0, -53.0 OR LESS, C4 CONNECTION TYPE (BOTTOM); 2.5?
 MIN. EDGE DISTANCE; CONCRETE SUBSTATE MAXIMUM ANCHOR
 SPACING IS 10.5?. CORRECT FOR ITEMS # 1-5.
  