Plan Review Notes For Permit 20070816 |
Permit Number |
20070816 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-31 10:33:28 | PLAN REVIEW - PLUMBING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. SUBMIT A NEW PLUMBING PLAN. PROVIDE SHOWER PAN | | DETAIL PER P2709.1 AND 2709.3. | | P2709.1 SHOWER PAN CONSTRUCTION. FBC 107.2.1 | | | | 2. PROVIDE NOTE FOR SHOWER CONTROL TEMPT. LIMITER PER | | P2708. | | P2708.4SHOWER CONTROL VALVES. | | | | 2. PLAN SHALL BE SIGNED AND SEALED BY DESIGNER OF | | RECORD. | | PLANS SUBMITTED FOR REVIEW SHALL HAVE THE NAME AND | | SIGNATURE OF DESIGNER OF RECORD SEC 107.3.4.1 | | | | | | | | |
|