Plan Review Notes For Permit 20070789 |
Permit Number |
20070789 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-31 14:45:16 | PLAN REVIEW GENERATOR FUEL GAS | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1) SUBMIT SPECS FOR THE FLEX CONNECTORS. SECTION R107.1 | | | | 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH | | MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET | | AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION | | G2421.1. | | | | | | |
|