Plan Review Notes For Permit 20070783
Permit Number 20070783
Review Stop E
Sequence Number 1
Notes
Date Text
2020-08-07 09:50:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) IS THERE A MASTER PERMIT ASSOCIATED WITH THIS
 PERMIT?
  
 2) IS THERE OTHERE SERVICES ON THIS BUILDING? ONLY ONE
 SERVIE TO A BUILDING
  
 230.2 NUMBER OF SERVICES A BUILDING OR OTHER STRUCTURE
 SERVED SHALL BE SUPPLIED BY ONLY ONE SER VICE UNLESS
 PERMITTED IN 230.2(A) THROUGH (D).
  
 3) LOAD CALCULATION 220
  
 220.40 GENERAL THE CALCULATED LOAD OF A FEEDER OR SE
 RVICE SHALL NOT BE LESS THAN THE SUM OF THE LOADS ON
 THE BRANCH CIRCUITS SUPPLIED, AS DETERMINED BY PART II
 OF THIS ARTICLE, AFTER ANY APPLICABLE DEMAND FACTORS
 PERMITTED BY PART III OR IV OR REQUIRED BY PART V HAVE
 BEEN APPLIED.
  
 4) FAULT CURRENT CALCULATION REQUIRED TO VERIFY AIC
 RATING OF SERVICE AND PANEL.
  
 5) NEED INTERIOR SPACE LAYOUT OF EQUIPMENT, OUTLETS,
 AND LIGHTING.
 110.9 INTERRUPTING RATING EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS SHALL HAVE AN
 INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE
 SUFFICIENT FOR THE CURRENT THAT IS AVAILABLE AT THE
 LINE TERMINALS OF THE EQUIPMENT