Plan Review Notes For Permit 20070783 |
Permit Number |
20070783 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-08-07 09:50:34 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) IS THERE A MASTER PERMIT ASSOCIATED WITH THIS | | PERMIT? | | | | 2) IS THERE OTHERE SERVICES ON THIS BUILDING? ONLY ONE | | SERVIE TO A BUILDING | | | | 230.2 NUMBER OF SERVICES A BUILDING OR OTHER STRUCTURE | | SERVED SHALL BE SUPPLIED BY ONLY ONE SER VICE UNLESS | | PERMITTED IN 230.2(A) THROUGH (D). | | | | 3) LOAD CALCULATION 220 | | | | 220.40 GENERAL THE CALCULATED LOAD OF A FEEDER OR SE | | RVICE SHALL NOT BE LESS THAN THE SUM OF THE LOADS ON | | THE BRANCH CIRCUITS SUPPLIED, AS DETERMINED BY PART II | | OF THIS ARTICLE, AFTER ANY APPLICABLE DEMAND FACTORS | | PERMITTED BY PART III OR IV OR REQUIRED BY PART V HAVE | | BEEN APPLIED. | | | | 4) FAULT CURRENT CALCULATION REQUIRED TO VERIFY AIC | | RATING OF SERVICE AND PANEL. | | | | 5) NEED INTERIOR SPACE LAYOUT OF EQUIPMENT, OUTLETS, | | AND LIGHTING. | | 110.9 INTERRUPTING RATING EQUIPMENT INTENDED TO | | INTERRUPT CURRENT AT FAULT LEVELS SHALL HAVE AN | | INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE | | SUFFICIENT FOR THE CURRENT THAT IS AVAILABLE AT THE | | LINE TERMINALS OF THE EQUIPMENT |
|