2020-07-29 15:18:49 | 07/29/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| FIREPLACE PER THE 2017 FBC FG SEC. 410.1. |
| 2. THE RANGE SPECS DID NOT LOAD CORRECTLY ON PROJECT |
| DOCS, PLEASE RELOAD, I CANNOT SEE IT PER THE WPB |
| AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| 3. ON ISOMETRIC BTU'S LIST DOES NOT MATCH AMOUNT OF |
| BTU?S, YOU DID NOT MULTIPLY THE TIKI TORCHES OR |
| LANTERN, IE. YOU HAVE FIVE TIKI AT 22 BTU?S TIME 5 |
| SHOULD EQUAL 110, YOU PUT ONLY 22 BTU?S, YOUR TOTAL |
| SHOULD BE 886 BTU?S AND YOU HAVE 791 TOTAL BTU?S, |
| PLEASE CORRECT ON BOTH SHEET OF ISO PER THE WPB |
| AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |