Plan Review Notes
Plan Review Notes For Permit 20070753
Permit Number 20070753
Review Stop G
Sequence Number 2
Notes
Date Text
2020-07-29 15:18:4907/29/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 FIREPLACE PER THE 2017 FBC FG SEC. 410.1.
 2. THE RANGE SPECS DID NOT LOAD CORRECTLY ON PROJECT
 DOCS, PLEASE RELOAD, I CANNOT SEE IT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 3. ON ISOMETRIC BTU'S LIST DOES NOT MATCH AMOUNT OF
 BTU?S, YOU DID NOT MULTIPLY THE TIKI TORCHES OR
 LANTERN, IE. YOU HAVE FIVE TIKI AT 22 BTU?S TIME 5
 SHOULD EQUAL 110, YOU PUT ONLY 22 BTU?S, YOUR TOTAL
 SHOULD BE 886 BTU?S AND YOU HAVE 791 TOTAL BTU?S,
 PLEASE CORRECT ON BOTH SHEET OF ISO PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  