Plan Review Notes For Permit 20070737 |
Permit Number |
20070737 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-08-18 05:41:41 | 1) THE DRINKING FOUNTAINS ARE LOCATED WITHIN THE | | ACCESSIBLE ROUTE. SUBMIT A DETAIL OF THE DRINKING | | FOUNTAINS AND SHOW THE DISTANCE OF THE LEADING EDGE OF | | THE DRINKING FOUNTAIN ABOVE THE FINISH FLOOR. COMPLY | | WITH FBC-ACCESS. SEC.307.2 FOR PROTRUDING OBJECTS. | | 2) SHT. A1.1.4 - DETAIL #1 - THE GRAB BARS SHALL BE | | MEASURED TO THE TOP OF THE GRIPPING SURFACE PER | | FBC-ACCESS. SEC. 609.4. | | 3) SHT. A1.1.4 - SHOW THE DEPTH OF THE STANDARD WATER | | CLOSET STALL ON THE PLANS. THE STALL DEPTH OF THE STALL | | SHALL COMPLY WITH FBC-PLUMBING SEC. 405.3.1. | | 4) SHT.A1.1.4 - SHOW THE LENGTH AND WIDTH DIMENSIONS OF | | THE HANDICAP ACCESSIBLE STALLS ON THE PLANS. | | 5) SUBMIT A SANITARY AND WATER DIAGRAM FOR THE CHANGES | | BEING MADE TO THE PLUMBING SYSTEM.WPB AMEND. TO FBC | | SEC. 107.3.5.1.3. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|