2020-09-28 09:53:41PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT THE SPECIFICATIONS FOR THE 16 KW GENERATOR
 THAT WILL BE INSTALLED. FBC 107.2
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET FROM
 OPENINGS INTO A BUILDING. FBC-R 303.5
  
  
  
  
  
  
  
  
  
  
  
  
  