2020-09-02 10:37:46 | 09/02/20 2 ND GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. |
| |
| 2. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO |
| THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. SUBMIT AN |
| ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL |
| CUT SECTIONS OF PIPE PER 2017 FBC RES. SECS. G2413.4.1, |
| G2413.4.2. |
| |
| 3. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC RES. SEC. G2413.2. |
| |
| 4. SUBMIT A COPY OF THE SIZING TABLE USED IN THE DESIGN |
| FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF |
| PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| SYSTEM PER THE 2017 FBC RES. SEC. G2413.3. |
| |
| 5. IF APPLICABLE SUBMIT MANUFACTURER'S SPECIFICATIONS |
| FOR THE PRESSURE REGULATORS. REGULATORS INSTALLED ON |
| THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR |
| OUTDOOR INSTALLATION PER THE 2017 FBC RES. SEC. |
| G2421.1. |
| |
| 6. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF |
| EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2. |
| |
| 7. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| THE 2017 FBC RES. SEC. G2401.1.3. |
| |
| 8. SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017 |
| FBC RES. SEC. G2419.2. |
| |
| 9. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC |
| SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 10. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 11. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2017 FBC FG SEC. 409.4, |
| 2017 FBC RES. SEC. G2420.4. |
| |
| 12. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE |
| PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 13. THE GENERATOR DISTANCE FROM THE BUILDING SHALL |
| COMPLY WITH MANUFACTURES SPECIFICATION INSTRUCTIONS |
| PLEASE PROVIDE MANUFACTURES SPECIFICATION PER THE WPB |
| AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. THE MANUFACTURER'S |
| SPECIFICATIONS FOR THE GENERATOR SHALL BE ONSITE FOR |
| FINAL GAS INSPECTION. THE GENERATOR SHALL BE LISTED AND |
| APPROVED. NFPA 58 SEC. 5.20.1. THE GENERATOR SHALL MEET |
| THE REQUIREMENTS OF UL 2200. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |