2020-08-12 14:39:091) THE SUBMITTED GAS DRAWING SHOWS A TOTAL BTU LOAD OF
 517,00 BTU'S. CITY RECORDS SHOW A LARGER EXISTING BTU
 LOAD ON THE SYSTEM. LIST THE BTU LOAD OF EACH APPLIANCE
 AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4
 AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21). THE TOTAL
 BTU LOAD ON THIS SYSTEM WITH THE GENERATOR IS 1,197, 00
 BTU'S. 2ND REQUEST.
 2) SHOW THE SIZE OF THE METALLIC PIPE AT THE OUTLET
 (CONSUMER'S SIDE) OF THE GAS METER. THE SIZE OF THIS
 PIPE SHALL COMPLY WITH FBC-GAS TABLE 402.4 (5) FOR THE
 DISTANCE FROM THE GAS METER TO THE MOST REMOTE
 REGULATOR ON THE SYSTEM. CITY RECORDS SHOW THIS
 DISTANCE AS 100 FEET. THIS DISTANCE AND BTU LOAD WILL
 DETERMINE THE PIPE SIZE AT THE OUTLET AT THE GAS
 METER.FBC-GAS SEC.402.1, 402.2.
 3) SUBMIT MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR
 THE REGULATOR. ONLY ONE SHEET OF THE SPECIFICATIONS HAS
 BEEN SUBMITTED. FBC-FUEL GAS SEC. 410.1, FBC RES. SEC.
 G2421.1. 2ND REQUEST.
 4) THERE ARE TWO DIFFERENT GAS DRAWINGS IN THIS
 SUBMITTAL. REMOVE OR VOID THE ONE THAT IS NOT
 APPLICABLE. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW