Plan Review Notes For Permit 20070654 |
Permit Number |
20070654 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-08-12 14:39:09 | 1) THE SUBMITTED GAS DRAWING SHOWS A TOTAL BTU LOAD OF | | 517,00 BTU'S. CITY RECORDS SHOW A LARGER EXISTING BTU | | LOAD ON THE SYSTEM. LIST THE BTU LOAD OF EACH APPLIANCE | | AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017 | | FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1) | | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4 | | AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21). THE TOTAL | | BTU LOAD ON THIS SYSTEM WITH THE GENERATOR IS 1,197, 00 | | BTU'S. 2ND REQUEST. | | 2) SHOW THE SIZE OF THE METALLIC PIPE AT THE OUTLET | | (CONSUMER'S SIDE) OF THE GAS METER. THE SIZE OF THIS | | PIPE SHALL COMPLY WITH FBC-GAS TABLE 402.4 (5) FOR THE | | DISTANCE FROM THE GAS METER TO THE MOST REMOTE | | REGULATOR ON THE SYSTEM. CITY RECORDS SHOW THIS | | DISTANCE AS 100 FEET. THIS DISTANCE AND BTU LOAD WILL | | DETERMINE THE PIPE SIZE AT THE OUTLET AT THE GAS | | METER.FBC-GAS SEC.402.1, 402.2. | | 3) SUBMIT MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR | | THE REGULATOR. ONLY ONE SHEET OF THE SPECIFICATIONS HAS | | BEEN SUBMITTED. FBC-FUEL GAS SEC. 410.1, FBC RES. SEC. | | G2421.1. 2ND REQUEST. | | 4) THERE ARE TWO DIFFERENT GAS DRAWINGS IN THIS | | SUBMITTAL. REMOVE OR VOID THE ONE THAT IS NOT | | APPLICABLE. WPB AMEND. TO FBC SEC. 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|