Plan Review Notes For Permit 20070654 |
Permit Number |
20070654 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-08-06 10:22:35 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR PAD INFORMATION SUBMITTED DOES NOT | | MEET THE REQUIREMENTS FOR PREFABRICATED SLABS. | | PREFABRICATED GENERATOR PADS ARE REQUIRED TO HAVE | | PRODUCT APPROVALS OR SITE SPECIFIC ENGINEERING FROM A | | FLORIDA LICENSED ENGINEER. FBC 107.3.4 |
|