Plan Review Notes For Permit 20070598 |
Permit Number |
20070598 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-08-10 17:00:11 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SPECIFY THE EMBED DEPTH, SIZE AND TYPES OF FASTENERS | | THAT ARE REQUIRED TO ANCHOR THE GENERATOR, TANK, | | PLATFORM AND STAIRS TO THE GENERATOR SLAB IN ORDER TO | | RESIST THE WIND LOADS. FBC 107.2.1 |
|