 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN
 HEADING ?ANCHOR SPACING? PROVIDE INFORMATION FROM
 SHEETS 10-11 FL13757-R6. EXAMPLE 2.5? MIN EDGE
 DISTANCE; SUBSTRATE POURED CONCRETE, MAXIMUM SPAN
 8?-8?, LOAD (PSF) 110; C2 CONNECTION TYPE, USING
 TAPCONS ANCHOR SPACING IS 7.5? MAXIMUM.
 2. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN
 HEADING ?ANCHOR SPACING? PROVIDE INFORMATION FROM
 SHEETS 10-11 FL13757-R6. EXAMPLE 2.5? MIN EDGE
 DISTANCE; SUBSTRATE HOLLOW CONCRETE BLOCK, MAXIMUM SPAN
 8?-8?, LOAD (PSF) 110; C2 CONNECTION TYPE, USING
 TAPCONS, THIS ANCHOR CONDITION IS NOT ACCEPTABLE AS PER
 ANCHOR NOTES SHEET 10.
  