Plan Review Notes
Plan Review Notes For Permit 20070557
Permit Number 20070557
Review Stop G
Sequence Number 1
Notes
Date Text
2020-08-04 16:26:2508/04/20 1ST GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING TANKLESS WATER HEATER. A FULL EVALUATION OF
 ALL GAS EQUIPMENT WILL BE DONE AT FIELD, IF NOT TO
 CODE, IT MAY NEED TO BE BOUT UP TO CODE COMPLIANCE AT
 OWNER EXPENSE.
  
 2. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 4. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 5. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
  
 6. PLEASE SHOW AND LABEL UNIONS IN FRONT OF REGULATOR
 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2.
  
 7. SHOW DRIP LEG AND LABEL ON EQUIPMENT INSTALLED PER
 THE 2017 FBC RES. SEC. G2419.2.
  
 8. PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2017 FBC FG SEC. 409.4 OR 2017 FBC
 RES. SEC. G2401.1.3.
  
 9. ON ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH
 OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES. SECS.
 G2413.4.1, G2413.4.2.
  
 10. PLEASE SHOW IF THERE IS A REGULATOR, DRIP LEG,
 UNION AND SHUTOFF VALVE ON TANKLESS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 11. PLEASE PROVIDE THE TOTAL BTU'S FOR THE SYSTEM ON
 ISOMETRIC PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 12. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT
 (TANKLESS) TO VERIFY COMPLIANCE WITH 2017 FBC RES. SEC.
 G2408.1.
  
 13. IF APPLICABLE, PLEASE SHOW HOUSE THE LOCATION OF
 THE TANKLESS WATER HEATER AND THE LOCATION AND DISTANCE
 OF ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE
 WATER HEATER. THE LOCATION OF THE WATER HEATER SHALL
 COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  