2020-08-04 16:26:25 | 08/04/20 1ST GAS/ REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| EXISTING TANKLESS WATER HEATER. A FULL EVALUATION OF |
| ALL GAS EQUIPMENT WILL BE DONE AT FIELD, IF NOT TO |
| CODE, IT MAY NEED TO BE BOUT UP TO CODE COMPLIANCE AT |
| OWNER EXPENSE. |
| |
| 2. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE |
| PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 3. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.1 GENERAL. |
| |
| 4. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. |
| |
| 5. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1. |
| |
| 6. PLEASE SHOW AND LABEL UNIONS IN FRONT OF REGULATOR |
| 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2. |
| |
| 7. SHOW DRIP LEG AND LABEL ON EQUIPMENT INSTALLED PER |
| THE 2017 FBC RES. SEC. G2419.2. |
| |
| 8. PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON GAS |
| ISOMERIC PER THE 2017 FBC FG SEC. 409.4 OR 2017 FBC |
| RES. SEC. G2401.1.3. |
| |
| 9. ON ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH |
| OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES. SECS. |
| G2413.4.1, G2413.4.2. |
| |
| 10. PLEASE SHOW IF THERE IS A REGULATOR, DRIP LEG, |
| UNION AND SHUTOFF VALVE ON TANKLESS PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 11. PLEASE PROVIDE THE TOTAL BTU'S FOR THE SYSTEM ON |
| ISOMETRIC PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 12. SUBMIT MANUFACTURER'S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT |
| (TANKLESS) TO VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. |
| G2408.1. |
| |
| 13. IF APPLICABLE, PLEASE SHOW HOUSE THE LOCATION OF |
| THE TANKLESS WATER HEATER AND THE LOCATION AND DISTANCE |
| OF ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE |
| WATER HEATER. THE LOCATION OF THE WATER HEATER SHALL |
| COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE |
| WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |