2020-08-10 17:03:57 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20070540 |
| ADD: 515 N. FLAGLER DR. |
| CONT: SOUTHERN AWNING |
| TEL: 561-586-0464 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: MON. AUGUST 10TH/2020 |
| ACTION: DENIED |
| |
| 1) THE SUBMITTED SITE PLAN IS A COPY OF AN ISSUED |
| PERMIT. ARCHITECTS ARE INCLUDED IN COPYRIGHT LAWS. ALSO |
| PAPER PLAN NOT AN DIGITAL ORIGINAL. |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| DIGITALLY SIGNED AND SEALED ENGINEERING PLANS, |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| |
| 2) THE PERMIT APPLICATION INDICATES IN THE SCOPE OF |
| WORK THIS IS A NEW CANOPY FRAME AND COVERING. THERE |
| WERE NO STRUCTURAL PLANS UPLOADED. |
| |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATIVE CODE SECTION: |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| OR STRUCTURES. |
| 107.3.5.1 COMMERCIAL BUILDINGS |
| 107.3.5.1.1. BUILDING |
| |
| MISSING CODE DATA: |
| SET BACK / SEPARATION (ASSUMED PROPERTY LINES) |
| STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| DESIGN LOADS |
| WIND REQUIREMENTS |
| |
| 2A) 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| |
| 2. RISK CATEGORY. |
| |
| 3. WIND EXPOSURE. |
| APPLICABLE WIND DIRECTION IF MORE THAN ONE WIND |
| EXPOSURE IS UTILIZED. TABLE 1609.7.2. HEIGHT AND |
| EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| |
| 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| THE DESIGN OF THE STRUCTURE, PSF. |
| |
| 6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| CONVERSION VULT TO VASD. |
| |
| 2B) RIGID AWNING. PERMANENT OR NON-REMOVABLE FABRIC. |
| FBC-B 3105.4.2.2. THE WIND DESIGN LOADS FOR ANY FABRIC |
| OR MEMBRANE COVERED STRUCTURE DESIGNED WITH A PERMANENT |
| OR NON-REMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON |
| THE FOLLOWING CRITERIA: |
| 1) MINIMUM WIND SPEED VELOCITY AS REQUIRED IN CHAPTER |
| 16 USING FIGURE 1609.3(3) 150 VULT, CATEGORY 1 |
| BUILDINGS. |
| 2) EXPOSURES B, C, OR D AS DEFINED IN CHAPTER 16. |
| 3) IF POST OR VERTICAL PIPE SHOW ANCHORING OF THE BASE, |
| TO RESIST THE MOMENT OF OVER TURNING. |
| |
| 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
2020-08-10 16:46:12 | IN REVIEW. JW 8/10/2020 |