2020-08-06 08:25:45 | TEMPORARY TRAILER |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 AND (102.2 |
| (E)) |
| 1) PLEASE SHOW THE USE (OCCUPANCY TYPE) PER FBC CHAPTER |
| 3. (PLEASE BE SPECIFIC AS TO THE USE, SUCH AS OFFICE OR |
| HOSPITAL) MAY NOT BE A COMPLETE LIST OF REQUIREMENTS - |
| PLAN REVIEW IS BASED ON THE BUILDING USE (OCCUPANCY |
| TYPE). |
| 2) PLEASE PROVIDE SIGNED AND SEALED SUPPORT AND TIE |
| DOWN DETAILS FROM AN ARCHITECT OR ENGINEER - SHOW THE |
| WIND DESIGN DATA USED (WIND SPEED, RISK CATEGORY, ETC.) |
| FBC 1609 |
| 3) PLEASE SHOW ALL ACCESSIBILITY ELEMENTS TO COMPLY |
| WITH FBC ACCESSIBILITY CODE. |
| 4) PLEASE PROVIDE A COMPLETED BUILDING PERMIT |
| APPLICATION FROM A CONTRACTOR LICENSED TO INSTALL THE |
| TRAILER. |
| 5) PLEASE PROVIDE A SIGNED AND SEALED SURVEY SHOWING |
| TRAILER SETBACKS, FLOOD ZONES PER THE LATEST FIRM AND |
| THE FINISHED FLOOR ELEVATION OF THE TRAILER. |
| |
| FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO |
| BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR - |
| IF YOUR ENGINEER OR ARCHITECT DOES NOT HAVE AN |
| ELECTRONIC OR DIGITAL SIGNATURE - PLEASE DROP OFF (CITY |
| HALL DROP BOX) THE ORIGINAL SIGNED AND SEALED |
| DRAWINGS/DOCUMENTS ALONG WITH A "PLAN REVIEW REQUEST |
| FORM" EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT |
| OR DRAWINGS. PLAN REVIEW REQUEST FORM CAN BE OBTAINED |
| BY E MAILING [email protected] AND ASKING FOR THE FORM |
| |