Plan Review Notes For Permit 20070475 |
Permit Number |
20070475 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-08-01 10:54:40 | PLAN REVIEW GENERATOR ? FUEL GAS | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1) ELECTRICAL APPLICATION INDICATES A 500 GAL. U/G TANK | | SHALL BE INSTALLED. GAS RISER AND GAS SUB-PERMIT | | INDICATE N/G TO BE INSTALLED. | | PLEASE CLARIFY. | | | | | | | | |
|