Plan Review Notes
Plan Review Notes For Permit 20070475
Permit Number 20070475
Review Stop B
Sequence Number 1
Notes
Date Text
2020-08-01 10:51:56PLAN REVIEW GENERATOR - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) STRUCTURAL DETAIL OF THE PRE-CAST GENERATOR PAD
 SHALL HAVE A VALID DIGITAL SIGNATURE OF THE DESIGN
 PROFESSIONAL PER FS 471 & FAC 61G15.
  
 2) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR WITH A
 VALID DIGITAL SIGNATURE OF THE DESIGNER AS REQUIRED FOR
 THE GENERATOR PAD ENGINEERING PER FBC 107.3.5.3 AND
 R301.2.
  
 3) ELECTRICAL APPLICATION INDICATES A 500 GAL. U/G TANK
 SHALL BE INSTALLED. GAS RISER AND GAS SUB-PERMIT
 INDICATE N/G TO BE INSTALLED.
 PLEASE CLARIFY.
  
 4) IF U/G TANK WILL BE INSTALLED INDICATE LOCATION OF
 TANK ON SURVEY.
  