2020-07-17 15:02:47 | WINDOWS |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) PLEASE PROVIDE AN ORIGINAL SIGNED AND SEALED WIND |
| DESIGN PRESSURES FOR THE OPENINGS FBC 1609 - THE WIND |
| PRESSURES PROVIDED ARE BASED ON WHETHER OR NOT THE |
| ADJACENT WINDOWS/ DOORS OR SHUTTERS MEET IMPACT - SINCE |
| WE DON'T KNOW WE WOULD NEED TO SAY THEY DON'T - SO WE |
| WOULD NEED TO USE THE NON IMPACT SIDE OF THE CHART - |
| WHICH HAS A HIGHER PRESSURE - AND THE PRODUCT APPROVALS |
| PROVIDED FOR THE WINDOWS WILL NOT MEET THE HIGHER |
| PRESSURES. YOU MAY WANT TO PROVIDE A WIND PRESSURE |
| ENGINEERING THAT SHOWS WIND ZONES 4 AND 5 - SINCE IT |
| APPEARS BY YOUR DRAWING THAT YOU ARE IN A WIND ZONE 4. |
| 2) PLEASE SHOW THE HEIGHT OF THE BUILDING ON YOUR FLOOR |
| PLAN. |
| |
| FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO |
| BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. |
| DRAWINGS DO NOT SHOW IN "ADOBE READER" AS |
| DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR |
| ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE |
| ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG |
| WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON |
| FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW |
| REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] |
| AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS |
| MAY TAKE 2 TO 3 WEEKS TO PROCESS, TO SEND TO PLAN |
| REVIEW - DUE TO LIMITED STAFF INSIDE THE BUILDING |
| DEPT.) |