2020-07-22 14:57:59 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT- 20070386 |
| 7/22/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE PLAN SHOWS A RELOCATED SINK IN THE MIDDLE OF THE |
| FLOOR WITH NO PLUMBING DETAILS. PLEASE PROVIDE SANITARY |
| ISOMETRIC AND WATER RISER DRAWINGS, AND A FLAT LINE |
| PLAN SHOWING THE POINTS OF CONNECTIONS TO THE EXISTING |
| DRAIN, VENT AND WATER LINES- SECTION 107.2.1 WPB. |
| |
| 2) THERE IS NO SIGNATURE, SEAL, OR TITLE BLOCK ON THE |
| PLAN. IF THE CORRECTED PLUMBING PLAN IS PREPARED BY AN |
| ENGINEER, IT SHALL BEAR THE ELECTRONIC SEAL AND |
| SIGNATURE OF THE ENGINEER OF PER FL. STATUTE 471.025 |
| AND SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE CODE. |
| IF THE CONTRACTOR OR QUALIFIER PREPARES THE CORRECTED |
| DRAWING, THEN IT SHALL BEAR THE SIGNATURE OF THE |
| CONTRACTOR OR QUALIFIER- SECTION 107.2.1 WPB, AND |
| FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |