2020-08-11 13:04:19PLAN REVIEW GENERATOR - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR PER FBC
 107.3.5.3 AND R301.2 AS REQUIRED FOR THE GENERATOR PAD
 ENGINEERING.
 THE DESIGN PRESSURES PROVIDED ARE THE MAX. ALLOWABLE
 PRESSURES FOR THE GENERATOR PAD. PLEASE REFERENCE THE
 ALLOWABLE DESIGN PRESSURE NOTE. A DESIGN PROFESSIONAL
 SHALL PROVIDE DESIGN WIND LOAD CALCULATIONS FOR THE
 SITE. THE PRESSURES PROVIDED FOR THE GENERATOR PAD MUST
 MEET OR EXCEED THESE WIND LOAD PRESSURES.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
  
 2) STRUCTURAL DETAIL OF PAD AND DESIGN LOADS SHALL BE
 SIGNED AND SEALED BY A DESIGN PROFESSIONAL.
 SEE COMMENTS UNDER SIGNATURE REVIEW.
  
  