2020-08-11 13:04:19 | PLAN REVIEW GENERATOR - BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 2ND REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR PER FBC |
| 107.3.5.3 AND R301.2 AS REQUIRED FOR THE GENERATOR PAD |
| ENGINEERING. |
| THE DESIGN PRESSURES PROVIDED ARE THE MAX. ALLOWABLE |
| PRESSURES FOR THE GENERATOR PAD. PLEASE REFERENCE THE |
| ALLOWABLE DESIGN PRESSURE NOTE. A DESIGN PROFESSIONAL |
| SHALL PROVIDE DESIGN WIND LOAD CALCULATIONS FOR THE |
| SITE. THE PRESSURES PROVIDED FOR THE GENERATOR PAD MUST |
| MEET OR EXCEED THESE WIND LOAD PRESSURES. |
| R301.2.1 WIND DESIGN CRITERIA. |
| BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| FROM FIGURE R301.2(4). |
| |
| |
| 2) STRUCTURAL DETAIL OF PAD AND DESIGN LOADS SHALL BE |
| SIGNED AND SEALED BY A DESIGN PROFESSIONAL. |
| SEE COMMENTS UNDER SIGNATURE REVIEW. |
| |
| |