Plan Review Notes
Plan Review Notes For Permit 20070360
Permit Number 20070360
Review Stop G
Sequence Number 1
Notes
Date Text
2020-07-28 14:36:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20070360 313 N LAKESIDE CT
  
  
 1ST REVIEW
 GAS COMMENTS: DENIED
 1. AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE GAS/PLUMBING
 PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR
 THE PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION
 NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR
 LICENSED IN THAT TRADE.
 2. PER WPB FBC 107.1, ALL PLANS TO BE SIGNED AND SEALED
 BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS. AS
 DESIGNER DOES NOT PROVIDE DIGITAL SIGNATURE IN
 ACCORDANCE WITH FAC AND FS, THEN THE DESIGNER SHALL
 PROVIDE PROPERLY SIGNED/SEALED PAPER DOCUMENT IN
 ACCORDANCE WITH FAC AND FS PRIOR TO PERMIT ISSUANCE.
 CALL 561-805-6724 FOR ADDITIONAL INFORMATION.
 3. PER FBC FC 409.2, EVERY METER SHALL BE EQUIPPED WITH
 A SHUTOFF VALVE LOCATED ON THE SUPPLY SIDE OF THE
 METER.
 4. PER WPB FBC 107.2.1, PROVIDE DOCUMENTATION THAT
 REGULATOR IS APPROVED FOR EXTERIOR APPLICATION.
 5. SITE SURVEY SHOWING LOCATIONS OF GAS METER AND
 GENERATOR IS NOT LEGIBLE. PER WPB FBC 107.2.1, SUBMIT A
 LEGIBLE DRAWING/SURVEY, CLEARLY SHOWING THE SHOWING
 LOCATIONS OF GAS METER AND GENERATOR.
 6. PER WPB FBC 107.2.1, SUBMIT THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 ALL PLANS TO BE SIGNED/ SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS. PLEASE SEE COMMENTS #1 AND #2
 ABOVE.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  