2020-07-09 07:36:47 | PLAN REVIEW - MECHANICAL |
| |
| PERMIT NUMBER - 20070299 - GARAGE CONVERSION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE ENERGY SUBMITTAL FOR GARAGE CONVERSION. |
| FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| PROVIDE ENERGY GAUGE FORM R405 PER SECTION R405.2 FBC |
| EC. |
| |
| PROVIDE THE MANUAL J WORKSHEETS WITH THE AC SYSTEM |
| SIZING CALCULATIONS- SECTION R403.7.1 FBC EC. |
| |
| 2. IDENTIFY LOCATION OF CU. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 3. PROVIDE SERVICE OUTLET AT CU. |
| EQUIPMENT SERVICE OUTLET: |
| E3901.12 HVAC OUTLET. |
| |
| |
| |
| |
| |